Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

127

P1080[3] Min.

frequency

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

0.00

P-Group: SETPOINT

Active: Immediately

QuickComm.: Yes Max: 650.00

Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint.

The minimum frequency P1080 represents a masking frequency of 0 Hz for all frequency target value
sources (e.g. ADC, MOP, FF, USS), with the exception of the JOG target value source (analogous to
P1091). Thus the frequency band +/- P1080 is run through in optimum time by means of the
acceleration/deceleration ramps. Dwelling in the frequency band is not possible (see example).

Furthermore, an undershoot of the actual frequency f_act below min. frequency P1080 is output by the
following signal function.

Index:

P1080[0] : 1st. Drive data set (DDS)
P1080[1] : 2nd. Drive data set (DDS)
P1080[2] : 3rd. Drive data set (DDS)

Example:

0

t

1

t

r0053
Bit 02

|f_act| > f_min

P1080

-P1080 - P2150

P1080 + P2150

-P1080

t

P1080

-P1080

0

t

1

ON/OFF

P2153 = 0

f_set

f_act

Note:

Value set here is valid both for clockwise and for anticlockwise rotation.

Under certain conditions (e.g. ramping, current limiting), motor can run below minimum frequency.