Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

37

r0056

CO/BO: Status of motor control

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: CONTROL

Max: -

Displays status of motor control (MM420: V/f status), which can be used to diagnose inverter status.

Bitfields:

Bit00 Init. control finished 0 NO 1 YES
Bit01 Motor demagnetizing finished 0 NO 1 YES
Bit02 Pulses enabled 0 NO 1 YES
Bit03 Voltage soft start selected 0 NO 1 YES

Bit04 Motor excitation finished 0 NO 1 YES
Bit05 Starting boost active 0 NO 1 YES
Bit06 Acceleration boost active 0 NO 1 YES
Bit07 Frequency is negative 0 NO 1 YES

Bit08 Field weakening active 0 NO 1 YES
Bit09 Volts setpoint limited 0 NO 1 YES
Bit10 Slip frequency limited 0 NO 1 YES
Bit11 F_out > F_max Freq. limited 0 NO 1 YES

Bit12 Phase reversal selected 0 NO 1 YES
Bit13 I-max controller active 0 NO 1 YES
Bit14 Vdc-max controller active 0 NO 1 YES
Bit15 KIB (Vdc-min control) active 0 NO 1 YES

Details:

See description of seven-segment display given in the introduction.

r0061

CO: Act. encoder frequency

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: CONTROL

Max: -

Displays actual frequency detected by encoder.

r0062

CO: Freq. setpoint

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: CONTROL

Max: -

Displays frequency setpoint of vector controller.

r0063

CO: Act. frequency

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: CONTROL

Max: -

Displays actual unfiltered frequency. This value is not smoothed in contrary to r0021.

V/f

0

1,2

SLVC

(Observer

model)

Encoder

P0400

P1300

160 ms

Act. frequencies:

Act. filtered frequency

Act. frequency

Act. encoder frequency

21,23

20,22

<20

0

P1300 = 21,23 and P0400 = 0 --> F0090

P0408

60

r0313

Act. filtered speed

r0313

60

r0022

r0021

r0063

r0061




Level

3

Level

2

Level

3

Level