Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

169

P1470[3]

Gain speed controller (SLVC)

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

-

Def:

3.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 2000.0

Enters gain of speed controller for sensorless vector control (SLVC).

r1438

r1084

Kp

Tn

P1470 P1472

r0064

P1496 P0341 P0342

P1489

P1488

P1452

Act. frequency
from observer model

r0063

r1170

Precontrol

Freq. setpoint

Torque

setpoint

Droop

150 ms

r1518

P1492

r1490

0

1

0

r0079

r1508

*)

*) only active , if pre-control is enabled
(P1496 > 0)

Index:

P1470[0] : 1st. Drive data set (DDS)
P1470[1] : 2nd. Drive data set (DDS)
P1470[2] : 3rd. Drive data set (DDS)

P1472[3]

Integral time n-ctrl. (SLVC)

Min: 25

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

400

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 32001

Enters integral time of speed controller for sensorless vector control (SLVC).

Index:

P1472[0] : 1st. Drive data set (DDS)
P1472[1] : 2nd. Drive data set (DDS)
P1472[2] : 3rd. Drive data set (DDS)

P1477[3]

BI: Set integrator of n-ctrl.

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 4000:0

Selects source to read in command to enable speed controller.

Index:

P1477[0] : 1st. Command data set (CDS)
P1477[1] : 2nd. Command data set (CDS)
P1477[2] : 3rd. Command data set (CDS)

P1478[3]

CI: Set integrator value n-ctrl.

Min: 0:0

CStat:

UT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 4000:0

Selects source for integral part of speed controller.

Index:

P1478[0] : 1st. Command data set (CDS)
P1478[1] : 2nd. Command data set (CDS)
P1478[2] : 3rd. Command data set (CDS)

Dependency:

In case of sensorless vector control, integrator freezing must be selected (Bit 1 "Integral freeze (SLVC)" of
P1400 has to be set) to save the integrator output.

Note:

-

If the setting command is not connected (P1477=0), a pending value is read in after pulse enable at the
end of the excitation time (P0346) and the integral component of the speed controller is set once.

-

If the P1482 (integral component of speed controller) is connected upon pulse enable, the integral
component of the controller is set to the last value prior the pulse inhibit.

-

Neither function works after flying start.

Level

2

Level

2

Level

3

Level

3