Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

188

6SE6400-5BB00-0BP0

3.30 Inverter

parameters

(Modulator)

P1800 Pulse

frequency

Min: 2

CStat:

CUT

Datatype: U16 Unit:

kHz

Def:

4

P-Group: INVERTER

Active: Immediately

QuickComm.: No

Max: 16

Sets pulse frequency of power switches in inverter. The frequency can be changed in steps of 2 kHz.

Dependency:

Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency).
-

see derating in P1082

-

P1800 > 30 * P0310

Note:

-

If the pulse frequency is increased, max. inverter current r0209 can be reduced (derating). The derating
characteristic depends on the type and power of the inverter (see manuall OPERATING
INSTRUCTION).

-

If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce
inverter losses and radio-frequency emissions.

-

Under certain circumstances, the inverter may reduce the switching frequency to provide protection
against over-temperature (see P0290).

r1801

CO: Act. pulse frequency

Min: -

Datatype: U16 Unit:

kHz

Def:

-

P-Group: INVERTER

Max: -

Actual pulse frequency of power switches in inverter.

Notice:

Under certain conditions (inverter overtemperature, see P0290), this can differ from the values selected in
P1800 (pulse frequency).

P1802 Modulator

mode

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: INVERTER

Active: first confirm

QuickComm.: No

Max: 2

Selects inverter modulator mode.

Possible Settings:

0

SVM/ASVM automatic mode

1 Asymmetric

SVM

2

Space vector modulation

Notice:

-

Asymmetric space vector modulation (ASVM) produces lower switching losses than space vector
modulation (SVM), but may cause irregular rotation at very low frequencies.

-

Space vector modulation (SVM) with over-modulation may produce current waveform distortion at high
output voltages.

-

Space vector modulation (SVM) without over-modulation will reduce maximum output voltage available
to motor.

P1803[3] Max.

modulation

Min: 20.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

106.0

P-Group: INVERTER

Active: Immediately

QuickComm.: No

Max: 150.0

Sets maximum modulation index.

Index:

P1803[0] : 1st. Drive data set (DDS)
P1803[1] : 2nd. Drive data set (DDS)
P1803[2] : 3rd. Drive data set (DDS)

Note:

-

P1803 = 100 % : Limit for over-control (for ideal inverter without switching delay).


-

For vector control the modulation limit will be reduced automatically with 4 %.

P1820[3]

Reverse output phase sequence

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: INVERTER

Active: first confirm

QuickComm.: No

Max: 1

Changes direction of motor rotation without changing setpoint polarity.

Possible Settings:

0 OFF
1 ON

Index:

P1820[0] : 1st. Drive data set (DDS)
P1820[1] : 2nd. Drive data set (DDS)
P1820[2] : 3rd. Drive data set (DDS)

Dependency:

If positive and negative revolution is enabled, frequency setpoint is directly used.
If both positive and negative revolution are disabled, reference value is set to zero.

Details:

See P1000 (select frequency setpoint)

Level

2

Level

3

Level

3

Level

4

Level

2