Siemens 440 User Manual

Page 118

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

118

6SE6400-5BB00-0BP0

P1021[3]

BI: Fixed freq. selection Bit 1

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines origin of fixed frequency selection.

Index:

P1021[0] : 1st. Command data set (CDS)
P1021[1] : 2nd. Command data set (CDS)
P1021[2] : 3rd. Command data set (CDS)

Dependency:

Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)

Details:

See P1020 (fixed frequency selection Bit 0) for most common settings

P1022[3]

BI: Fixed freq. selection Bit 2

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines origin of fixed frequency selection.

Index:

P1022[0] : 1st. Command data set (CDS)
P1022[1] : 2nd. Command data set (CDS)
P1022[2] : 3rd. Command data set (CDS)

Dependency:

Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)

Details:

See P1020 (fixed frequency selection Bit 0) for most common settings

P1023[3]

BI: Fixed freq. selection Bit 3

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

722:3

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines origin of fixed frequency selection.

Index:

P1023[0] : 1st. Command data set (CDS)
P1023[1] : 2nd. Command data set (CDS)
P1023[2] : 3rd. Command data set (CDS)

Dependency:

Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)

Details:

See P1020 (fixed frequency selection Bit 0) for most common settings

r1024

CO: Act. fixed frequency

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: SETPOINT

Max: -

Displays sum total of selected fixed frequencies.

P1025[3]

Fixed frequency mode - Bit 4

Min: 1

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 2

Direct selection or direct selection + ON for bit 4

Possible Settings:

1 Direct

selection

2

Direct selection + ON command

Index:

P1025[0] : 1st. Command data set (CDS)
P1025[1] : 2nd. Command data set (CDS)
P1025[2] : 3rd. Command data set (CDS)

Details:

See parameter P1001 for description of how to use fixed frequencies.

P1026[3]

BI: Fixed freq. selection Bit 4

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

722:4

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines origin of fixed frequency selection.

Index:

P1026[0] : 1st. Command data set (CDS)
P1026[1] : 2nd. Command data set (CDS)
P1026[2] : 3rd. Command data set (CDS)

Dependency:

Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO).

Details:

See P1020 (fixed frequency selection Bit 0) for most common settings.

Level

3

Level

3

Level

3

Level

3

Level

3

Level

3

Advertising