Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

162

6SE6400-5BB00-0BP0

3.29.1.1 Slip

compensation

P1335[3] Slip

compensation

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

0.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 600.0

Dynamically adjusts output frequency of inverter so that motor speed is kept constant independent of motor
load.

In the V/f-control, the motor speed will always be less than the command speed due to the slip speed. For a
given speed command, the speed will drop as load is increased. The speed regulation of drive can be
improved by the technique known as slip compensation.

Increasing the load from M1 to M2 (see diagram) will decrease the motor speed from f1 to f2, due to the
slip. The inverter can compensate for this by increasing the output frequency slightly as the load increases.
The inverter measures the current and increases the output frequency to compensate for the expected slip.

Without slip compensation

M

f

f

f

2

f

1

M

2

M

1

With slip compensation

M

f

f

f

2

f

1

M

2

M

1

f

out M1

f

out M2

Index:

P1335[0] : 1st. Drive data set (DDS)
P1335[1] : 2nd. Drive data set (DDS)
P1335[2] : 3rd. Drive data set (DDS)

Value:

P1335 = 0 % :
Slip compensation disabled.

P1335 = 50 % - 70 % :
Full slip compensation at cold motor (partial load).

P1335 = 100 % :
Full slip compensation at warm motor (full load).

f

f

N

out

6 % 10 %

P1335

100 %

%

f

f

N

set

6 % 10 %

f

f

N

out

Range of slip compensation :

without

slip compensation

with

slip compensation

Notice:

The applied value of the slip compensation (scaled by P1335) is limited by following equation:

Setpoint

channel

100

1335

P

f

Slip_act

f

set

f

Slip_comp_max

P1335

f

act

r0065

r1078

r0063

r0330

100

P1336

f

max

Slip_comp_

=

f

out

r1337

Level

2