Siemens 440 User Manual

Page 80

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

80

6SE6400-5BB00-0BP0

P0706[3]

Function of digital input 6

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

15

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 99

Selects function of digital input 6.

Possible Settings:

0

Digital input disabled

1 ON/OFF1
2

ON reverse /OFF1

3

OFF2 - coast to standstill

4

OFF3 - quick ramp-down

9 Fault

acknowledge

10 JOG

right

11 JOG

left

12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
25 DC brake enable
29 External

trip

33 Disable additional freq setpoint
99 Enable BICO parameterization

Index:

P0706[0] : 1st. Command data set (CDS)
P0706[1] : 2nd. Command data set (CDS)
P0706[2] : 3rd. Command data set (CDS)

Details:

See P0701 (function of digital input 1).

P0707[3]

Function of digital input 7

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 99

Selects function of digital input 7 (via analog input).

Possible Settings:

0

Digital input disabled

1 ON/OFF1
2

ON reverse /OFF1

3

OFF2 - coast to standstill

4

OFF3 - quick ramp-down

9 Fault

acknowledge

10 JOG

right

11 JOG

left

12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
25 DC brake enable
29 External

trip

33 Disable additional freq setpoint
99 Enable BICO parameterization

Index:

P0707[0] : 1st. Command data set (CDS)
P0707[1] : 2nd. Command data set (CDS)
P0707[2] : 3rd. Command data set (CDS)

Note:

Signals above 4 V are active, signals below 1,6 V are inactive.

Details:

See P0701 (function of digital input 1).

Level

2

Level

2

Advertising