Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

109

r0968 Status

word

1

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: COMM

Max: -

Displays active status word of inverter (in binary) and can be used to diagnose which commands are active.

Bitfields:

Bit00 Drive ready 0 NO 1 YES
Bit01 Drive ready to run 0 NO 1 YES
Bit02 Drive running 0 NO 1 YES
Bit03 Drive fault active 0 NO 1 YES

Bit04 OFF2 active 0 YES 1 NO
Bit05 OFF3 active 0 YES 1 NO
Bit06 ON inhibit active 0 NO 1 YES
Bit07 Drive warning active 0 NO 1 YES

Bit08 Deviation setpoint / act. value 0 YES 1 NO
Bit09 PZD control 0 NO 1 YES
Bit10 Maximum frequency reached 0 NO 1 YES
Bit11 Warning: Motor current limit 0 YES 1 NO

Bit12 Motor holding brake active 0 NO 1 YES
Bit13 Motor overload 0 YES 1 NO
Bit14 Motor runs right 0 NO 1 YES
Bit15 Inverter overload 0 YES 1 NO

P0970 Factory

reset

Min: 0

CStat:

C

Datatype: U16 Unit:

-

Def:

0

P-Group: PAR_RESET

Active: first confirm

QuickComm.: No

Max: 1

P0970 = 1 resets all parameters to their default values.

Possible Settings:

0 Disabled
1 Parameter

reset

Dependency:

-

First set P0010 = 30 (factory settings).

-

Stop drive (i.e. disable all pulses) before you can reset parameters to default values.

Note:

The following parameters retain their values after a factory reset:

-

P0014 Store mode

-

r0039 CO: Energy consumption meter [kWh]

-

P0100 Europe / North America

-

P0918 CB address

-

P2010 USS baud rate

-

P2011 USS address

P0971

Transfer data from RAM to EEPROM

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 1

Transfers values from RAM to EEPROM when set to 1.

Possible Settings:

0 Disabled
1 Start

transfer

Note:

All values in RAM are transferred to EEPROM.

Parameter is automatically reset to 0 (default) after successful transfer.

The storage from RAM to EEPROM is accomplished via P0971. The communications are reset, if the
transfer was successful. During the reset process communications will be interrupted. This creates the
following conditions:
-

PLC (e.g. SIMATIC S7) enters Stop mode

-

Starter automatically recovers communications once they are re-established.

-

Drivemonitor is displayed "NC" (not connected) in the status line or "drive busy".

-

BOP displays "busy"


After completion of the transfer process, the communication between the inverter and the PC-tools (e.g.
Starter) or BOP is automatically re-established.

Level

3

Level

1

Level

3