Siemens 440 User Manual

Page 198

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

198

6SE6400-5BB00-0BP0

P2014[2]

USS telegram off time

Min: 0

CStat:

CT

Datatype: U16 Unit:

ms

Def:

0

P-Group: COMM

Active: Immediately

QuickComm.: No

Max: 65535

Defines the telegram failure time for the serial interfaces with USS protocol.

The telegram failure time defines the time within which a valid telegram must have been received. If a valid
telegram is not received within the specified time, the drive inverter outputs fault F0070.

Index:

P2014[0] : Serial interface COM link
P2014[1] : Serial interface BOP link

Notice:

By default (time set to 0), no fault is generated (i.e. watchdog disabled).

r2015[8]

CO: PZD from BOP link (USS)

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: COMM

Max: -

Displays process data received via USS on BOP link (RS232 USS).

STX
LGE

ADR

Start of text
Length

Address

PKW

PZD
BCC

Parameter ID value

Process data
Block check character

USS telegram

PZD mapping to parameter r2015

.

.

.

r2033

r2032

STW
HSW

Control word
Main setpoint

USS on BOP link

[0]

r2015

[1]
[2]
[3]

[7]

PZD1

STW1

PZD2

HSW

PZD3

PZD4

STW2

P2012

STX

LGE

ADR

BCC

PKW

PZD

Process data

Parameter

Index:

r2015[0] : Received word 0
r2015[1] : Received word 1
r2015[2] : Received word 2
r2015[3] : Received word 3
r2015[4] : Received word 4
r2015[5] : Received word 5
r2015[6] : Received word 6
r2015[7] : Received word 7

Note:

The control words can be viewed as bit parameters r2032 and r2033.

Restrictions:
-

If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.

-

If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the
2nd PZD-word,

-

When P2012 is greater than or equal to 4 the additional control word (2nd control word) must
transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).

Level

3

Level

3