36 load torque monitoring – Siemens 440 User Manual

Page 218

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

218

6SE6400-5BB00-0BP0

P2179

Current limit for no load ident.

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

3.0

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10.0

Threshold current for A0922 (load missing) in [%] relative to P0305 (rated motor current) as illustrated in the
diagram below.

0

1

r2197 Bit11

0

1

0

&

Cur.lim:no-load ID

0.0 ... 10.0 [%]

P2179 (3.0)

Load missing delay

0 ... 10000 [ms]

P2180 (2000)

| V_act |

Pulse_enable

| I_act |

Load missing

Load missing

T 0

Note:

-

It may be that the motor is not connected (load missing) or a phase could be missing.

-

If a motor setpoint cannot be entered and the current limit (P2179) is not exceeded, Alarm A0922 (no
load applied) is issued when delay time (P2180) expires.

P2180

Delay time for load missing

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

2000

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Delay time to identify that the current is less than the threshold defined in P2179.

Details:

See diagram in P2179 (current limit for no load identification).

3.36

Load torque monitoring

P2181[3]

Belt failure detection mode

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: ALARMS

Active: first confirm

QuickComm.: No

Max: 6

Parameter P2181 activates or de-activates the load torque monitoring and defines the response to a load
torque fault.

Using the load torque monitoring, it is possible to detect a mechanical failure or an overload condition of the
mechanical transmission line, e.g. a broken drive belt or a stalled conveyor belt. In this case, the actual
torque/frequency actual value is compared to a programmed envelope characteristic (refer to P2182 -
P2190). If the actual torque/frequency actual value lies above or below the envelope curve, then after the
delay time P2192 expires, as a function of P2181, alarm A0952 is output or the drive inverter is tripped with
fault message F0452.

Possible Settings:

0

Belt failure detection disabled

1

Warning: Low torque / frequency

2

Warning: High torque / frequency

3

Warning: High / low torque / frequency

4

Trip: Low torque / frequency

5

Trip: High torque / frequency

6

Trip: High / low torque / frequency

Index:

P2181[0] : 1st. Command data set (CDS)
P2181[1] : 2nd. Command data set (CDS)
P2181[2] : 3rd. Command data set (CDS)

Level

3

Level

3

Level

2