Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

185

P1755[3]

Start-freq. motor model (SLVC)

Min: 0.1

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

5.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 250.0

Enter the start frequency of sensorless vector control (SLVC), thereby SLVC switches over from open-loop
to closed-loop at that frequency.
The default setting depends on the motor power:
-

0 kW to 0.749 kW: 5.0 Hz

-

0.75 kW to 75 kW: 1.5 Hz

-

75.1 kW to 200 kW: 1.0 Hz

SLVC open loop

SLVC closed loop

P1758

t

[%]

100

[%]

P1756

[Hz]

P1755

[Hz]

P1756

=

f_act

t

P1755
P1756 [Hz]

Index:

P1755[0] : 1st. Drive data set (DDS)
P1755[1] : 2nd. Drive data set (DDS)
P1755[2] : 3rd. Drive data set (DDS)

P1756[3]

Hyst.-freq. motor model (SLVC)

Min: 10.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

50.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 100.0

Enters hysteresis frequency (in percent of start-frequency) to switch back from sensorless-vector-control
(SLVC) to current model.

Value is entered in the range 0 % to 50 % relative to P1755 (SLVC stop frequency).

Index:

P1756[0] : 1st. Drive data set (DDS)
P1756[1] : 2nd. Drive data set (DDS)
P1756[2] : 3rd. Drive data set (DDS)

P1758[3]

Chng-ov. del. t SLVC op.-lp ctrl

Min: 100

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

1500

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 2000

Sets the minimum time when the changeover frequency is fallen below when changing from the closed-loop
into the open-loop controlled mode.

Index:

P1758[0] : 1st. Drive data set (DDS)
P1758[1] : 2nd. Drive data set (DDS)
P1758[2] : 3rd. Drive data set (DDS)

Dependency:

Refer to P1750, P1755, P1756

P1759[3]

Chng-ov. del. t SLVC cl.-lp ctrl

Min: 50

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

100

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 2000

Sets the minimum time when the changeover frequency is exceeded when changing from the open-loop
controlled into the closed-loop controlled mode.

Index:

P1759[0] : 1st. Drive data set (DDS)
P1759[1] : 2nd. Drive data set (DDS)
P1759[2] : 3rd. Drive data set (DDS)

Dependency:

Refer to P1750, P1755, P1756

Level

3

Level

3

Level

3

Level

3