Siemens 440 User Manual

Page 49

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

49

P0292 Inverter

temperature

warning

Min: 0

CStat:

CUT

Datatype: U16 Unit:

°C

Def:

5

P-Group: INVERTER

Active: first confirm

QuickComm.: No

Max: 25

Defines the temperature difference (in ºC) between the Overtemperature trip threshold and the warning
threshold of the inverter. The trip threshold is stored internally by the inverter and cannot be changed by the
user.

Temperature

MM440, Frame Size

110 °C
140 °C

95 °C

145 °C

A - C

D - F

Input rectifier

-

Cooling air

-

Control board

-

80 °C

145 °C

F

600 V

-

-

-

-

-

-

88 °C

150 °C

FX

95 kW

CT

91 °C

150 °C

110 kW

CT

75 °C
55 °C

75 °C
55 °C

65 °C

65 °C

80 °C

145 °C

GX

132 kW

CT

82 °C

147 °C

160 kW

CT

75 °C
55 °C

75 °C
55 °C

65 °C

65 °C

88 °C

150 °C

200 kW

CT

75 °C
50 °C

65 °C

IGBT

Heat sink

trip

T

= T - P0292

Temperature warning threshold of inverter T_warn

Temperature shutdown threshold of inverter T_trip

warn


If the actual inverter temperature (r0037) exceeds the corresponding threshold, a warning A0504, if the
temperature still increases then a fault F0004 will be displayed.

P0294

Inverter I2t overload warning

Min: 10.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

95.0

P-Group: INVERTER

Active: first confirm

QuickComm.: No

Max: 100.0

Defines the [%] value at which alarm A0505 (inverter I2t) is generated.

Inverter I2t calculation is used to determine a maximum tolerable period for inverter overload. The I2t
calculation value is deemed = 100 % when this maximum tolerable period is reached.

Dependency:

That the output current of the inverter has been reduced and that the value of I2t does not exceed 100%.

Note:

P0294 = 100 % corresponds to stationary nominal load.

P0295

Inverter fan off delay time

Min: 0

CStat:

CUT

Datatype: U16 Unit:

s

Def:

0

P-Group: TERMINAL

Active: first confirm

QuickComm.: No

Max: 3600

Defines inverter fan switch off delay time in seconds after drive has stopped.

Note:

Setting to 0, inverter fan will switch off when the drive stops, that is no delay.