Siemens 440 User Manual

Page 193

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

193

Caution:

Parameter P2000 represents the reference frequency of the above mentioned interfaces. A maximum
frequency setpoint of 2*P2000 can be applied via the corresponding interface. Unlike parameter P1082
(Max. Frequency) this limits the inverter frequency internally independent of the reference frequency. By
modification of P2000 it will also adapt the parameter to the new settings.

PZD

ADC

f (Hex)

f [Hz]

Setpoint

channel

Motor

control

f_act

f_act,limit

P1082

2000

P

%

100

f(%)

2000

P

4000(Hex)

f(Hex)

f[Hz]

=

=

f_act,limit = min(P1082, f_act)

f (%)

Normalization

Limitation

Notice:

Reference variables are intended as an aid to presenting setpoint and actual value signals in a uniform
manner. This also applies to fixed settings entered as a precentage. A value of 100 % (USS / CB)
corresponds to a process data value of 4000H, or 4000 0000H in the case of double values.

In this respect, the following parameters are available:

Reference frequency

Reference voltage

Reference current

Reference torque

Hz

V
A

Nm

P2000

P2001
P2002

P2003

Reference power

kW

hp

P2004

f(P0100)

P2001[3] Reference

voltage

Min: 10

CStat:

CT

Datatype: U16 Unit:

V

Def:

1000

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 2000

Full-scale output voltage (i.e. 100 % ) used over serial link (corresponds to 4000H).

Index:

P2001[0] : 1st. Drive data set (DDS)
P2001[1] : 2nd. Drive data set (DDS)
P2001[2] : 3rd. Drive data set (DDS)

Example:

P2001 = 230 specifies that 4000H received via USS denotes 230 V.

If a BICO connection is made between two parameters, the "unit" of the parameters (standardized (Hex) or
physical (i.e. V) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target
value.

P0771

DAC

r0026

x[V]

y[Hex]

]

Hex

[

4000

P2001[V]

r0026[V]

y[Hex]

=

Level

3

Advertising