17 fixed frequencies – Siemens 440 User Manual

Page 113

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

113

3.17 Fixed

frequencies

P1001[3]

Fixed frequency 1

Min: -650.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

0.00

P-Group: SETPOINT

Active: Immediately

QuickComm.: No

Max: 650.00

Defines fixed frequency setpoint 1.

There are three options available for selection of the fixed frequencies:
1. Direct

selection

2. Direct selection + ON command
3. Binary coded selection + ON command

1. Direct selection (P0701 - P0706 = 15):

-

In this mode of operation 1 digital input selects 1 fixed frequency.

-

If several inputs are active together, the selected frequencies are summed.

-

E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.


2. Direct selection + ON command (P0701 - P0706 = 16):

-

The fixed frequency selection combines the fixed frequencies with an ON command.

-

In this mode of operation 1 digital input selects 1 fixed frequency.

-

If several inputs are active together, the selected frequencies are summed.

-

E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.


3. Binary coded selection + ON command (P0701 - P0706 = 17):

-

Up to 16 fixed frequencies can be selected using this method.

-

The fixed frequencies are selected according to the following table:

Index:

P1001[0] : 1st. Drive data set (DDS)
P1001[1] : 2nd. Drive data set (DDS)
P1001[2] : 3rd. Drive data set (DDS)

Example:

DIN4

DIN3

DIN2

DIN1

FF0

P1001

FF1

0 Hz

0

0

0

0

0

0

0

1

0

0

1

0

0

0

1

1

0

1

0

0

0

1

0

1

0

1

1

0

0

1

1

1

1

0

0

0

1

0

0

1

1

0

1

0

1

0

1

1

1

1

0

0

1

1

0

1

1

1

1

0

P1002

FF2

P1003

FF3

P1004

FF4

P1005

FF5

P1006

FF6

P1007

FF7

P1008

FF8

P1010

FF9

P1011

FF10

P1012

FF11

P1013

FF12

P1014

FF13

P1015

FF14

P1009

FF15

1

1

1

1

Binary coded selection :

Level

2

Advertising