Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

42

6SE6400-5BB00-0BP0

3.3 Inverter

parameters

(HW)

P0100

Europe / North America

Min: 0

CStat:

C

Datatype: U16 Unit:

-

Def:

0

P-Group: QUICK

Active: first confirm

QuickComm.: Yes Max: 2

Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in [kW] or [hp].

The default settings for the nominal rating plate frequency (P0310) and maximum motor frequency (P1082)
are also set automatically here, in addition to reference frequency (P2000).

Possible Settings:

0

Europe [kW], frequency default 50 Hz

1

North America [hp], frequency default 60 Hz

2

North America [kW], frequency default 60 Hz

Dependency:

Where:
-

Stop drive first (i.e. disable all pulses) before you change this parameter.

-

P0100 can only be changed when P0010 = 1 (Commissioning mode) via the respective Commissioing
interface (e.g. BOP).

-

Changing P0100 resets all rated motor parameters as well as other parameters that depend on the
rated motor parameters (see P0340 - calculation of motor parameters).


Changing P0100 overwrites the settings of the DIP50/60 switch (location shown in the diagram below):
1. Parameter P0100 has an higher priority than the DIP50/60 switch.
2. However, after the inverter is powered-on again and P0100 < 2, the DIP50/60 setting will take priority

and overwrite P0100.

3. The DIP50/60 switch does not have any effect, if P0100 = 2.

R

em

ov

e I

/O

boar

d

DIP50/60

P0100 = 2

?

P0100 = 0

DIP50/60 =

50 Hz

?

P0100 = 2

P0100 = 1

P0100 = 2

?

P0100 = 1

?

yes

no

yes

yes

yes

no

no

no

Quick

commissioning

P0010 = 1

Power

cycle

Power in kW

Frequency 50 Hz

Power in kW

Frequency 60 Hz

Power in hp

Frequency 60 Hz

Notice:

P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see
diagram above).

P0199

Equipment system number

Min: 0

CStat:

UT

Datatype: U16 Unit:

-

Def:

0

P-Group: -

Active: first confirm

QuickComm.: No

Max: 255

Equipment system number This parameter has no operation effect.

Level

1

Level

2