Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

89

ADC1

ADC2

OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA

1 2

3 4

5 6 7 8 9

OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA

Possible Settings:

0

Unipolar voltage input (0 to +10 V)

1

Unipolar voltage input with monitoring (0 to 10 V)

2

Unipolar current input (0 to 20 mA)

3

Unipolar current input with monitoring (0 to 20 mA)

4

Bipolar voltage input (-10 V to +10 V)

Index:

P0756[0] : Analog input 1 (ADC 1)
P0756[1] : Analog input 2 (ADC 2)

Notice:

When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F0080) if
the analog input voltage falls below 50 % of the deadband voltage.

On account of h/w restirction it is not possible to select the bipolar voltage (see Enum declaration) for
analog input 2 (P0756[1] = 4).

Details:

See P0757 to P0760 (ADC scaling).

P0757[2]

Value x1 of ADC scaling [V / mA]

Min: -20

CStat:

CUT

Datatype: Float Unit:

-

Def:

0

P-Group: TERMINAL

Active: first confirm

QuickComm.: No

Max: 20

Parameters P0757 - P0760 configure the input scaling as shown in the diagram:

ASPmax

100 %

10 V
20 mA

V
mA

x

100%

%

P0760

P0758

P0757

P0759

P0756 = 0 ... 3, P0761 = 0

ASPmin

4000 h


Where:
-

Analog setpoints represent a [%] of the normalized frequency in P2000.

-

Analog setpoints may be larger than 100 %.

-

ASPmax represents highest analog setpoint (this may be at 10 V or 20 mA).

-

ASPmin represents lowest analog setpoint (this may be at 0 V or 20 mA).

-

Default values provide a scaling of 0 V or 0 mA = 0 %, and 10 V or 20 mA = 100 %.