Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

184

6SE6400-5BB00-0BP0

SLVC open loop means that the speed controller does not get any frequency feedback from the observer
model.

.

.

r0062

Speed

controller

Pre-

control

Torque

limitation

Current

controller

i

sq

open/closed

loop

Flux setpoint

closed loop

Flux setpoint

open loop

i

sd

P1610

P1611

+

+

0

Act. output

voltage

Act. output

frequency

Act. frequency

Current

measurement

Act. angle

Observer model

closed loop

Slip

Frequency

setpoint

i

u

i

w

i

v

P1452

P1470 P1472

P1750/P1755

Bitfields:

Bit00 Start SLVC open loop 0 NO 1 YES
Bit01 Zero crossing SLVC open loop 0 NO 1 YES

Index:

P1750[0] : 1st. Drive data set (DDS)
P1750[1] : 2nd. Drive data set (DDS)
P1750[2] : 3rd. Drive data set (DDS)

r1751

Status word of motor model

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: CONTROL

Max: -

Displays status of transition from feed-forward to observer-control and vice versa.

Bitfields:

Bit00 Transit to SLVC open loop 0 NO 1 YES
Bit01 N-adaption enabled 0 NO 1 YES
Bit02 Transit to SLVC closed loop 0 NO 1 YES
Bit03 Speed controller enabled 0 NO 1 YES

Bit04 Current injection 0 NO 1 YES
Bit05 Start flux decrease 0 NO 1 YES
Bit14 Rs adapted 0 NO 1 YES
Bit15 Xh adapted 0 NO 1 YES

Level

3