19 jog – Siemens 440 User Manual

Page 122

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

122

6SE6400-5BB00-0BP0

3.19 JOG

P1055[3]

BI: Enable JOG right

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of JOG right.

Index:

P1055[0] : 1st. Command data set (CDS)
P1055[1] : 2nd. Command data set (CDS)
P1055[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.8 = JOG right via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

P1056[3]

BI: Enable JOG left

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of JOG left.

Index:

P1056[0] : 1st. Command data set (CDS)
P1056[1] : 2nd. Command data set (CDS)
P1056[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.9 = JOG left via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

Level

3

Level

3

Advertising