9 digital inputs, Issue 01/06 parameter description – Siemens 440 User Manual

Page 77

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

77

3.9 Digital

inputs

P0701[3]

Function of digital input 1

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 99

Selects function of digital input 1.

DIN channel (e.g. DIN1 - PNP (P0725 = 1))

24 V

T

0

&

0

1

PNP/NPN DIN

0 ... 1

P0725 (1)

0 V

24

V

Debounce time: DIN

0 ... 3

P0724 (3)

CO/BO: Bin.inp.val

r0722

r0722

.0

Kl.9
P24 (PNP)
Kl.28

0 V (NPN)

Pxxxx BI : ...

P0701

Function

0

1

Possible Settings:

0

Digital input disabled

1 ON/OFF1
2

ON reverse /OFF1

3

OFF2 - coast to standstill

4

OFF3 - quick ramp-down

9 Fault

acknowledge

10 JOG

right

11 JOG

left

12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
17 Fixed setpoint (Binary coded selection + ON)
25 DC brake enable
29 External

trip

33 Disable additional freq setpoint
99 Enable BICO parameterization

Index:

P0701[0] : 1st. Command data set (CDS)
P0701[1] : 2nd. Command data set (CDS)
P0701[2] : 3rd. Command data set (CDS)

Dependency:

Setting 99 (enable BICO parameterization) requires
-

P0700 command source or

-

P0010 = 1, P3900 = 1, 2 or 3 quick commissioning or

-

P0010 = 30, P0970 = 1 factory reset in order to reset.

Notice:

Setting 99 (BICO) for expert use only.

Level

2

Advertising