Issue 01/06 parameter description – Siemens 440 User Manual

Page 197

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

197

P2013[2]

USS PKW length

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

127

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 127

Defines the number of 16-bit words in PKW part of USS telegram.

The PKW part consists of the PKE part (1. word), IND part (2. word) resp. PWE part (3. - n. word). In
contrary to the IND and PKE part, the PWE part can be varied. Depending on the particular requirement, 3-
word, 4-word or variable word lengths can be parameterized. The PKW part of the USS telegram is used to
read and write individual parameter values.

Possible Settings:

0 No

words

3 3

words

4 4

words

127 Variable

Index:

P2013[0] : Serial interface COM link
P2013[1] : Serial interface BOP link

Example:

Parameter access fault

U16 (16 Bit)

U32 (32 Bit)

Float (32 Bit)

P2013 = 3

X

P2013 = 4

X

X

X

P2013 = 127

X

X

X

Parameter access fault

Data type

Notice:

USS protocol consists of PZD and PKW which can be changed by the user via parameters P2012 and
P2013 respectively. Parameter P2013 determines the number of PKW-words in a USS-telegram.

Setting P2013 to 3 or 4 determines the length of the PKW (3 = three words and 4 = four words). When
P2013 set to 127 automatically adjusts the length of the PKW words are required.

P2013 = 3

P2013 = 4

1 word

each 16 Bit

PKE

IND

PWE

P2013

PKE

IND

PWE

P2013

PKE
IND
PWE

Parameter ID

Sub-index
Parameter value


If a fixed PKW length is selected only one parameter value can be transferred. In the case of indexed
parameter, you must use the variable PKW length if you wish to have the values of all indices transferred in
a single telegram. In selecting the fixed PKW length, it is important to ensure the value in question can be
transferred using this PKW length.

P2013 = 3, fixes PKW length, but does not allow access to many parameter values. A parameter fault is
generated when an out-of-range value is used, the value will not be accepted but the inverter state will not
be affected. Useful for applications where parameters are not changed, but MM3s are also used. Broadcast
mode is not possible with this setting.

P2013 = 4, fixes PKW length. Allows access to all parameters, but indexed parameters can only be read
one index at a time. Word order for single word values are different to setting 3 or 127, see example below.

P2013 = 127, most useful setting. PKW reply length varies depending on the amount of information needed.
Can read fault information and all indices of a parameter with a single telegram with this setting.

Example:
Set P0700 to value 5 (0700 = 2BC (hex))

P2013 = 3

Master

MM4

22BC 0000 0005

22BC 0000 0000 0005

22BC 0000 0005 0000

MM4

Master

12BC 0000 0005

12BC 0000 0000 0005

12BC 0000 0005

P2013 = 4

P2013 = 127

Level

3