Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

214

6SE6400-5BB00-0BP0

P2166[3]

Delay time ramp up completed

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Delay time for signal that indicates completion of ramp-up.

Index:

P2166[0] : 1st. Drive data set (DDS)
P2166[1] : 2nd. Drive data set (DDS)
P2166[2] : 3rd. Drive data set (DDS)

Details:

See diagram in P2174.

P2167[3]

Switch-off frequency f_off

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

1.00

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10.00

Defines the threshold of the monitoring function |f_act| <= P2167 (f_off).

P2167 influences following functions:
-

If the actual frequency falls below this threshold and the time delay has expired, bit 1 in status word 2
(r0053) is reset.

-

If a OFF1 or OFF3 was applied and bit 1 is reset the inverter will disable the pulse (OFF2).

Restriction:
-

The monitoring function |f_act| <= P2167 (f_off) is not updated and pulses are not disabled, if motor
holding brake (MHB, P1215 = 1) is enabled.

|f|

t

0

1

P2168

t

t

r0053
Bit 01

OFF2

P2167

Active

Inactive

act

f

P2168

P2168

OFF1/OFF3

|f_act| > P2167

OFF1/OFF3

ON

t

Index:

P2167[0] : 1st. Drive data set (DDS)
P2167[1] : 2nd. Drive data set (DDS)
P2167[2] : 3rd. Drive data set (DDS)

P2168[3]

Delay time T_off

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Defines time for which the inverter may operate below switch-off frequency (P2167) before switch off
occurs.

Index:

P2168[0] : 1st. Drive data set (DDS)
P2168[1] : 2nd. Drive data set (DDS)
P2168[2] : 3rd. Drive data set (DDS)

Dependency:

Active if holding brake (P1215) not parameterized.

Details:

See diagram in P2167 (switch-off frequency)




Level

2

Level

3

Level

3