Siemens 440 User Manual

Page 135

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

135

P1135[3]

OFF3 ramp-down time

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

s

Def:

5.00

P-Group: SETPOINT

Active: first confirm

QuickComm.: Yes Max: 650.00

Defines ramp-down time from maximum frequency to standstill for OFF3 command.

f

f max

(P1082)

f

2

0

P1135

t

down,OFF3

P1082

f

P1135

t

2

3

OFF

,

down

=

OFF3

P2168

P2167

r0052 Bit02

Operation

Pulse

cancellation

t

t

t

P2168

f

act,motor

f

act,inverter

Index:

P1135[0] : 1st. Drive data set (DDS)
P1135[1] : 2nd. Drive data set (DDS)
P1135[2] : 3rd. Drive data set (DDS)

Note:

This time may be exceeded if the VDC_max. level is reached.

P1140[3]

BI: RFG enable

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

1:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines command source of RFG enable command (RFG: ramp function generator). If binary input is equal
to zero then the RFG output will be set immediately to 0.

Index:

P1140[0] : 1st. Command data set (CDS)
P1140[1] : 2nd. Command data set (CDS)
P1140[2] : 3rd. Command data set (CDS)

P1141[3]

BI: RFG start

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

1:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines command source of RFG start command (RFG: ramp function generator). If binary input is equal to
zero then the RFG output is held at it present value.

Index:

P1141[0] : 1st. Command data set (CDS)
P1141[1] : 2nd. Command data set (CDS)
P1141[2] : 3rd. Command data set (CDS)

P1142[3]

BI: RFG enable setpoint

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

1:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines command source of RFG enable setpoint command (RFG: ramp function generator). If binary input
is equal to zero then the RFG input will be set to zero and the RFG output will be ramp-down to zero.

Index:

P1142[0] : 1st. Command data set (CDS)
P1142[1] : 2nd. Command data set (CDS)
P1142[2] : 3rd. Command data set (CDS)

r1170

CO: Frequency setpoint after RFG

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: SETPOINT

Max: -

Displays overall frequency setpoint after ramp generator.

Level

2

Level

3

Level

3

Level

3

Level

3

Advertising