6 control commands & status information, Control commands & status information – Lenze E94AxHE Technology Application CiA402 Device profile User Manual

Page 140

Advertising
background image

9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Interpolated position mode

140

L

EDS94TA11010xxxx EN 1.2 - 03/2010

3.11.6

Control commands & status information

The CiA402 (

0x6040

) control word serves to execute control commands in the

"interpolated position mode":

The CiA402 (

0x6041

) status word serves to output the following status information in the

"interpolated position mode":

Internal states/state changes

[3-3]

Internal state changes

Control word

Status Function

Bit 4

0 "Interpolated position mode" is not active

0 Ê 1 Select "Interpolated position mode"
1 Ì 0 Deselect "Interpolated position mode"

Bit 5

0 Reserved (bit must be set to "0")

Bit 6

0 Reserved (bit must be set to "0")

Bit 8

0 Ê 1 Stop

Status word

Status Meaning

Bit 12

0 "Interpolated position mode" is not active
1 "Interpolated position mode" is active

Bit 13

0 Reserved (bit is always set to "0")

n

"Interpolated position mode" is selected via bit 4 of the control word.

• The "interpolation is not active" status occurs.

• Setpoints are accepted by the master control and buffered for the interpolation, but the axis is not

moving yet.

o

Interpolation is enabled.

• It is changed to the internal "Interpolation is active" status.

• The drive accepts input data and moves the axis.

p

"Interpolated position mode" is deselected again (bit 4 of the control word is reset).

• It is changed back to the internal "Interpolation is not active" status.

q

Another operating mode is selected via the control word.

Operation enabled

Interpolation inactive

Interpolation active

Œ



Ž



Disable voltage

Shutdown

Quick stop