9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Cyclic synchronous torque mode (IEC 61800-7)

164

L

EDS94TA11010xxxx EN 1.2 - 03/2010

3.14.6

Control commands & status information

The CiA402 (

0x6040

) control word serves to execute control commands in the "cyclic

synchronous torque mode":

The CiA402 (

0x6041

) status word serves to output the following status information in the

" cyclic synchronous torque mode":

Control word

Status Function

Bit 4

0 Reserved (bit must be set to "0")

Bit 5

0 Reserved (bit must be set to "0")

Bit 6

0 Reserved (bit must be set to "0")

Bit 8

0 Ê 1 Stop

Status word

Status Meaning

Bit 12

0 "Cyclic synchronous torque mode" is not active
1 "Cyclic synchronous torque mode" is active

Bit 13

0 Reserved (bit is always set to "0")