9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Device control

0x6041 - Status word

Index | Name:

0x6041 | Status word

Data type: UNSIGNED_16

Code:

C03531

Status word from the drive.



Device states

Value is bit-coded:

Information

Bit 0 Ready to switch on

Device state "Device is ready to start"

Bit 1 Switched on

Device state "Device is switched on"

Bit 2 Operation enabled

Device state "Operation"

Bit 3 Fault

Device state "Fault"

Bit 4 Voltage enabled

DC-bus voltage available

Bit 5 Quick stop

Quick stop active

Bit 6 Switch on disabled

Switch on inhibit is active

Bit 7 Warning

Warning active

Bit 8 Following error

Following error

• The difference between position setpoint and actual

position value is higher than the window set in

0x6065

.

Bit 9 Remote

Drive can receive commands via the fieldbus.

Bit 10 Target reached

Drive has reached target position.

• The actual position value is in the position window

set in

0x6067

.

Bit 11 Reserved
Bit 12 Homing attained or operation mode

active

Operating mode-dependent status bit:

• Homing mode: homing executed.

• Other operating modes: operating mode is active.

Bit 13 Homing error

Operating mode-dependent status bit:

• Homing mode: fault during homing.

• Other operating modes: reserved.

Bit 14 Home position available

Home position available

Bit 15 Reserved

;

Read access … Write access … CINH … PLC-STOP … PDO_MAP_RX ; PDO_MAP_TX