EDS94TA11010xxxx EN 1.2 - 03/2010

L

61

9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Device control

3.7.5

Stop

The standard stop of the drive will be automatically activated by the internal state

machine if the operating mode selected in the

0x6060

object (mode of operation) is

deactivated again and the drive is not yet at standstill.

 The drive is braked to standstill via a parameterisable deceleration ramp.

– While the drive is braked to standstill, C02530 displays the "Drive is stopped"

function state.

– If meanwhile another basic drive function is activated, this basic function will take

over control of the drive from the current speed on and the function state "Drive is

stopped" is abandoned.

– If the drive is at standstill, C02530 will display the basic state "Drive at standstill".

 An acceleration phase active at the time of activating the stopping process is

considered by the standard stop, i.e. the current acceleration is first led to "0" with the

parameterised S-ramp time before the real deceleration process starts.

 If the controller is enabled while the shaft is coasting (controller inhibit and pulse

inhibit are deactivated), the drive will be braked from the current speed to standstill.

Lenze parameters for the "Stop" basic function:

Parameter

Lenze setting

Value Unit

C02610

Deceleration time for stop

0.000 s

C02612

Ref. for decel. time of stop

Motor reference speed (C00011)