0x607e, 0x6089, 0x608a – Lenze E94AxHE Technology Application CiA402 Device profile User Manual

Page 65: Parameter setting & configuration factor group

Advertising
background image

EDS94TA11010xxxx EN 1.2 - 03/2010

L

65

9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Factor group

0x607E - Polarity

0x6089 - Position notation index

0x608A - Position dimension index

Index | Name:

0x607E | Polarity

Data type: UNSIGNED_8

Code:

C03583

Mounting directions

Subindex Name



0x607E/1

Polarity of motor



0x607E/2

Polarity of load

Index | Name:

0x607E/1 | Polarity of motor

Data type: UNSIGNED_32

Code: C02527

Motor mounting direction

• Direct mapping of the Lenze code C02527 (motor mounting direction).
Setting range

(min. value | unit | max. value)

Lenze setting

0

1 1

;

Read access ; Write access ; CINH … PLC-STOP … PDO_MAP_RX … PDO_MAP_TX

Index | Name:

0x607E/2 | Polarity of load

Data type: UNSIGNED_32

Code: C02529

Position encoder mounting dir.

• Direct mapping of the Lenze code C02529 (position encoder mounting direction).
Setting range

(min. value | unit | max. value)

Lenze setting

0

1 1

;

Read access ; Write access ; CINH … PLC-STOP … PDO_MAP_RX … PDO_MAP_TX

Index | Name:

0x6089 | Position notation index

Data type: INTEGER_8

Code:

C03550

Multiplier for position values (10 exp value, decimal point)
Setting range

(min. value | unit | max. value)

Lenze setting

0

0 0

;

Read access ; Write access … CINH … PLC-STOP … PDO_MAP_RX … PDO_MAP_TX

Index | Name:

0x608A | Position dimension index

Data type: UNSIGNED_8

Code:

C03551

Unit for position values
Setting range

(min. value | unit | max. value)

Lenze setting

0

0 0

;

Read access ; Write access … CINH … PLC-STOP … PDO_MAP_RX … PDO_MAP_TX