0x607c, 0x6098, Parameter setting & configuration homing mode – Lenze E94AxHE Technology Application CiA402 Device profile User Manual

Page 76

Advertising
background image

9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Homing mode

76

L

EDS94TA11010xxxx EN 1.2 - 03/2010

0x607C - Home position

0x6098 - Homing method

Index | Name:

0x607C | Home position

Data type: INTEGER_32

Code: C02642

Position which is set as current position during a reference search in the home position or when setting the

reference.

• Direct illustration of the Lenze code C02642 (reference position).
Setting range

(min. value | unit | max. value)

Lenze setting

-2147483647

pos unit

2147483647 0 pos unit

;

Read access ; Write access … CINH … PLC-STOP … PDO_MAP_RX … PDO_MAP_TX

Index | Name:

0x6098 | Homing method

Data type: INTEGER_8

Code:

C03601

All CiA402 homing methods are supported.

• If "0" is selected, the homing modes will be selected via the 0x55AF (Lenze code C02640) manufacturer-specific

object instead.

Selection list

(Lenze setting printed in bold)

Information

-2 Lenze cw_Trq_Lim

"Homing to limit stop"

(Lenze homing mode 14)

-1 Lenze ccw_Trq_Lim

"Homing to limit stop"

(Lenze homing mode 15)

0 Lenze homing mode

The homing is done according to the Lenze homing mode

selected in 0x55AF (Lenze code C02640)

1 Homing method 01 acc. to DS401

Homing methods according to CiA402

... Homing method ... acc. to DS401

35 DS401 homing method 35

;

Read access ; Write access … CINH … PLC-STOP … PDO_MAP_RX … PDO_MAP_TX