0x60fe/1, 0x60fe, Object (physical – Lenze E94AxHE Technology Application CiA402 Device profile User Manual

Page 39: Parameter setting & configuration common entries

Advertising
background image

EDS94TA11010xxxx EN 1.2 - 03/2010

L

39

9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Common entries

0x60FE - Digital outputs

Index | Name:

0x60FE | Digital outputs

Data type: UNSIGNED_8

Code:

C03516

Data structure for the digital outputs.

Subindex Name



0x60FE/1

Physical outputs



0x60FE/2

Bit mask

Index | Name:

0x60FE/1 | Physical outputs

Data type: UNSIGNED_8

Code:

C03517

Status of the digital outputs.

0: LOW level

1: HIGH level
Value is bit-coded:

Information

Bit 0 Reserved

-

Bit 1 DO2

Digital output 2

Bit 2 DO3

Digital output 3

Bit 3 DO4

Digital output 4

Bit 4 State bus out

Output signal - state bus

Bit 5 User LED

User LED

Bit 6 Reserved

-

Bit 7 Reserved

-

;

Read access ; Write access … CINH … PLC-STOP ; PDO_MAP_RX … PDO_MAP_TX

Index | Name:

0x60FE/2 | Bit mask

Data type: UNSIGNED_8

Code:

C03518

Bit masking of the digital outputs.

0: output is inhibited.

1: output is enabled.
Value is bit-coded:

Information

Bit 0 Reserved

-

Bit 1 DO2

Digital output 2

Bit 2 DO3

Digital output 3

Bit 3 DO4

Digital output 4

Bit 4 State bus out

Output signal - state bus

Bit 5 User LED

User LED

Bit 6 Reserved

-

Bit 7 Reserved

-

;

Read access ; Write access … CINH … PLC-STOP … PDO_MAP_RX … PDO_MAP_TX