C03683 | torque offset, C03684 | positive speed limit, C03685 | negative speed limit – Lenze E94AxHE Technology Application CiA402 Device profile User Manual

Page 217: C03686 | positive torque limit, C03687 | negative torque limit, C03688 | max torque, Code, C03688, C03683, C03684

Advertising
background image

EDS94TA11010xxxx EN 1.2 - 03/2010

L

217

9400 Technology applications | CiA402 device profile

Parameter reference

Parameter list | C03683

C03683

C03684

C03685

C03686

C03687

C03688

Parameter | Name:

C03683 | Torque offset

Data type: INTEGER_32

Index: 20892

d

= 519C

h



CiA402 object

0x60B2

Setting range

(min. value | unit | max. value)

Lenze setting

-2147483648

2147483647 0

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C03684 | Positive speed limit

Data type: INTEGER_32

Index: 20891

d

= 519B

h



CiA402 object

0x60F6.1

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

175.00 100.00

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 100

Parameter | Name:

C03685 | Negative speed limit

Data type: INTEGER_32

Index: 20890

d

= 519A

h



CiA402 object

0x60F6.2

Setting range

(min. value | unit | max. value)

Lenze setting

-175.00

0.00 -100.00

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 100

Parameter | Name:

C03686 | Positive torque limit

Data type: UNSIGNED_16

Index: 20889

d

= 5199

h



CiA402 object

0x60E0

Setting range

(min. value | unit | max. value)

Lenze setting

0

32767 16384

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C03687 | Negative torque limit

Data type: UNSIGNED_16

Index: 20888

d

= 5198

h



CiA402 object

0x60E1

Setting range

(min. value | unit | max. value)

Lenze setting

0

32767 16384

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C03688 | Max torque

Daten type: UNSIGNED_16

Index: 20887

d

= 5197

h



CiA402 object

0x6072

Setting range

(min. value | unit | max. value)

Lenze setting

0

32767 32767

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Advertising