PLC programming

Project planning

Configuring I/O modules

8

8.4

8.4.4

l

345

EDSTCXN EN 2.0

8.4.4.2

CAN slave configuration

ETC107

Module ID: ID number of the module.

Node ID: The node ID is entered in the CAN parameter tab.

ETCxM Input/Output address: The basic addresses must always be stated as
word addresses. The address defines where the process data of the module
are located within the process image (I/O memory). This also determines to
which PLC task the data will be allocated. The following table shows the
allocation of the process image to the individual PLC tasks:

Task no.

I/O range

from

to

1

%W0

%W1023

2

%W1024

%W1535

3

%W1536

%W1791

4

%W1792

%W2047

Further information can be found in the chapter "Addressing" (

349).

ETCxC Input/Output address: The basic addresses must be issued as word
addresses within the range of %QW64 / %IW64 to %QW127 / %IW127.

Further information can be found in the chapter "Addressing" (

349).

Diagnostic address: This field will not be evaluated by the control.

Basic parameters