PLC programming

Project planning
Configuring I/O modules

8

8.4
8.4.4

l

348

EDSTCXN EN 2.0

[1000]
ParameterName=DeviceType
ObjectType=0x7
DataType=0x7
AccessType=ro
PDOMapping=0
DefaultValue=0x30191

Additional information

General information

Special functionality

I/O functionality

Device Profile Number

31

24 23

16 15

0

Bit 16: Digital inputs
Bit 17: Digital outputs
Bit 18: Analogue inputs
Bit 19: Analogue outputs

To disable the check of the number of IOs the DefaultValue = 0x191 has to
be set. If a module also transfers analogue data with the 1st Tx/Rx PDO, the
DefaultValue = 0xC0191 must be set, i.e. the support for digital I/Os must be
disabled.

8.4.4.4

Searching for configured CANopen modules

The control searches for all modules configured in the control configuration
before starting the actual communication (via PDO) with the module.

Searching for the modules is done via NodeGuarding, if configured,
otherwise via SDO Transfer (reading of Object index 1000

hex

).

For CANopen modules which do not support NodeGuarding or SDO Transfer,
searching for modules can be disabled. For this a 0 must be entered in the
EDS file for the CANopen module for the object entry 1000

hex

(Device Profil

Number).

Extract from an EDS file

Description of object index
1000hex

I/O functionality

Disable check

Disable search