4-50

489 Generator Management Relay

GE Multilin

4.9 S8 RTD TEMPERATURE

4 SETPOINTS

4

4.9.2 RTDS 1 TO 6

PATH: SETPOINTS

ÖØ

S8 RTD TEMPERATURE

ÖØ

RTD #1(6)

RTDs 1 through 6 default to Stator RTD type. There are individual alarm and trip configurations for each RTD. This allows
one of the RTDs to be turned off if it malfunctions. The alarm level is normally set slightly above the normal running temper-
ature. The trip level is normally set at the insulation rating. Trip voting has been added for extra reliability in the event of
RTD malfunction. If enabled, a second RTD must also exceed the trip temperature of the RTD being checked before a trip
will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD name may be changed if
desired.

„ RTD #1
„ [ENTER] for more

RTD #1 APPLICATION:

Stator

Range: Stator, Bearing, Ambient, Other, None

RTD #1 NAME:

Range: 8 alphanumeric characters

RTD #1 ALARM:

Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5.

RTD #1 ALARM

TEMPERATURE: 130°C

Range: 1 to 250°C in steps of 1

RTD #1 ALARM

EVENTS: Off

Range: On, Off

RTD #1 TRIP:

Off

Range: Off, Latched, Unlatched

RTD #1 TRIP VOTING:

RTD #1

Range: RTD #1 to RTD #12

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

RTD #1 TRIP

TEMPERATURE: 155°C

Range: 1 to 250°C in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE