GE 489 User Manual

Page 14

Advertising
background image

1-6

489 Generator Management Relay

GE Multilin

1.2 SPECIFICATIONS

1 INTRODUCTION

1

Timing Accuracy:

±0.5 s or ±0.5% of total time

Elements:

Trip and Alarm

OVERCURRENT ALARM

Pick-up Level:

0.10 to 1.50

× FLA in steps of 0.01

average phase current

Time Delay:

0.1 to 250.0 s in steps of 0.1

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Alarm

OFFLINE OVERCURRENT

Pick-up Level:

0.05 to 1.00

× CT in steps of 0.01

of any one phase

Time Delay:

3 to 99 cycles in steps of 1

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

+50ms at 50/60 Hz

Elements:

Trip

INADVERTENT ENERGIZATION

Arming Signal:

undervoltage and/or offline from breaker
status

Pick-up Level:

0.05 to 3.00

× CT in steps of 0.01

of any one phase

Time Delay:

no intentional delay

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

+50 ms at 50/60 Hz

Elements:

Trip

PHASE OVERCURRENT

Voltage Restraint:

Programmable fixed characteristic

Pick-up Level:

0.15 to 20.00

× CT in steps of 0.01

of any one phase

Curve Shapes:

ANSI, IEC, IAC, Flexcurve, Definite Time

Time Delay:

0.000 to 100.000 s in steps of 0.001

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

+50 ms at 50/60 Hz or ±0.5% total time

Elements:

Trip

NEGATIVE SEQUENCE OVERCURRENT

Pick-up Level:

3 to 100% FLA in steps of 1

Curve Shapes:

I

2

2

t trip defined by k, definite time alarm

Time Delay:

0.1 to 100.0 s in steps of 0.1

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

±100ms or ± 0.5% of total time

Elements:

Trip and Alarm

GROUND OVERCURRENT

Pick-up Level:

0.05 to 20.00

× CT in steps of 0.01

Curve Shapes:

ANSI, IEC, IAC, Flexcurve, Definite Time

Time Delay:

0.00 to 100.00 s in steps of 0.01

Pickup Accuracy:

as per Ground Current Input

Timing Accuracy:

+50 ms at 50/60 Hz or ±0.5% total time

Elements:

Trip

PHASE DIFFERENTIAL

Pick-up Level:

0.05 to 1.00

× CT in steps of 0.01

Curve Shape:

Dual Slope

Time Delay:

0 to 100 cycles in steps of 1

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

+50 ms at 50/60 Hz or ±0.5% total time

Elements:

Trip

GROUND DIRECTIONAL

Pickup Level:

0.05 to 20.00

× CT in steps of 0.01

Time Delay:

0.1 to 120.0 s in steps of 0.1

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip and Alarm

HIGH-SET PHASE OVERCURRENT

Pickup Level:

0.15 to 20.00

× CT in steps of 0.01

Time Delay:

0.00 to 100.00 s in steps of 0.01

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

±50 ms at 50/60 Hz or ±0.5% total time

Elements:

Trip

UNDERVOLTAGE

Pick-up Level:

0.50 to 0.99

× rated V in steps of 0.01

Curve Shapes:

Inverse Time, definite time alarm

Time Delay:

0.2 to 120.0 s in steps of 0.1

Pickup Accuracy:

as per Voltage Inputs

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip and Alarm

OVERVOLTAGE

Pick-up Level:

1.01 to 1.50

× rated V in steps of 0.01

Curve Shapes:

Inverse Time, definite time alarm

Time Delay:

0.2 to 120.0 s in steps of 0.1

Pickup Accuracy:

as per Voltage Inputs

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip and Alarm

VOLTS/HERTZ

Pick-up Level:

1.00 to 1.99

× nominal in steps of 0.01

Curve Shapes:

Inverse Time, definite time alarm

Time Delay:

0.1 to 120.0 s in steps of 0.1

Pickup Accuracy:

as per voltage inputs

Timing Accuracy:

±100 ms at

≥ 1.2 × Pickup

±300 ms at

< 1.2 × Pickup

Elements:

Trip and Alarm

VOLTAGE PHASE REVERSAL

Configuration:

ABC or ACB phase rotation

Timing Accuracy:

200 to 400 ms

Elements:

Trip

UNDERFREQUENCY

Required Voltage:

0.50 to 0.99

× rated voltage in Phase A

Block From Online:

0 to 5 sec. in steps of 1

Pick- up Level:

20.00 to 60.00 in steps of 0.01

Curve Shapes:

1 level alarm, two level trip definite time

Time Delay:

0.1 to 5000.0 sec. in steps of 0.1

Pickup Accuracy:

±0.02 Hz

Timing Accuracy:

±100 ms or ±0.5% of total time

Advertising