Hardware functional tests, 1 output current accuracy, 2 phase voltage input accuracy – GE 489 User Manual

Page 215: 2 hardware functional tests, Output current accuracy -3, Phase voltage input accuracy -3

Advertising
background image

GE Multilin

489 Generator Management Relay

7-3

7 TESTING

7.2 HARDWARE FUNCTIONAL TESTS

7

7.2HARDWARE FUNCTIONAL TESTS

7.2.1 OUTPUT CURRENT ACCURACY

The specification for output and neutral end current input is

±0.5% of 2 × CT when the injected current is less than 2 × CT.

Perform the steps below to verify accuracy.

1.

Alter the following setpoint:

S2 SYSTEM SETUP

Ö

CURRENT SENSING

Ö

PHASE CT PRIMARY:

"1000 A"

2.

Measured values should be

±10 A. Inject the values shown in the table below and verify accuracy of the measured val-

ues. View the measured values in:

A2 METERING DATA

ÖØ

CURRENT METERING

7.2.2 PHASE VOLTAGE INPUT ACCURACY

The specification for phase voltage input accuracy is

±0.5% of full scale (200 V). Perform the steps below to verify accu-

racy.

1.

Alter the following setpoints:

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

Ö

VT CONNECTION TYPE:

"Wye"

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

ÖØ

VOLTAGE TRANSFORMER RATIO:

"10.00:1"

2.

Measured values should be

±1.0 V. Apply the voltage values shown in the table and verify accuracy of the measured

values. View the measured values in:

A2 METERING DATA

ÖØ

VOLTAGE METERING

INJECTED CURRENT

EXPECTED

CURRENT

MEASURED CURRENT

1 A UNIT

5 A UNIT

PHASE A

PHASE B

PHASE C

0.1 A

0.5 A

100 A

0.2 A

1.0 A

200 A

0.5 A

2.5 A

500 A

1 A

5 A

1000 A

1.5 A

7.5 A

1500 A

2 A

10 A

2000 A

APPLIED LINE-

NEUTRAL VOLTAGE

EXPECTED VOLTAGE

READING

MEASURED VOLTAGE

A-N

B-N

C-N

30 V

300 V

50 V

500 V

100 V

1000 V

150 V

1500 V

200 V

2000 V

270 V

2700 V