489 Generator Management Relay

GE Multilin

6.3 MODBUS MEMORY MAP

6 COMMUNICATIONS

6

2525

RTD #5 TRIP

0 to 2

1

F115

0

2526

RTD #5 TRIP VOTING

1 to 12

1

F122

5

2527

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2528

RTD #5 TRIP TEMPERATURE

1 to 250

1

°C

F1

155

2529

RTD #5 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #6

2560

RTD #6 APPLICATION

0 to 4

1

F121

1

2561

RTD #6 ALARM

0 to 2

1

F115

0

2562

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2563

RTD #6 ALARM TEMPERATURE

1 to 250

1

°C

F1

130

2564

RTD #6 ALARM EVENTS

0 to 1

1

F105

0

2565

RTD #6 TRIP

0 to 2

1

F115

0

2566

RTD #6 TRIP VOTING

1 to 12

1

F122

6

2567

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2568

RTD #6 TRIP TEMPERATURE

1 to 250

1

°C

F1

155

2569

RTD #6 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #7

25A0

RTD #7 APPLICATION

0 to 4

1

F121

2

25A1

RTD #7 ALARM

0 to 2

1

F115

0

25A2

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

25A3

RTD #7 ALARM TEMPERATURE

1 to 250

1

°C

F1

80

25A4

RTD #7 ALARM EVENTS

0 to 1

1

F105

0

25A5

RTD #7 TRIP

0 to 2

1

F115

0

25A6

RTD #7 TRIP VOTING

1 to 12

1

F122

7

25A7

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

25A8

RTD #7 TRIP TEMPERATURE

1 to 250

1

°C

F1

90

25A9

RTD #7 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #8

25E0

RTD #8 APPLICATION

0 to 4

1

F121

2

25E1

RTD #8 ALARM

0 to 2

1

F115

0

25E2

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

25E3

RTD #8 ALARM TEMPERATURE

1 to 250

1

°C

F1

80

25E4

RTD #8 ALARM EVENTS

0 to 1

1

F105

0

25E5

RTD #8 TRIP

0 to 2

1

F115

0

25E6

RTD #8 TRIP VOTING

1 to 12

1

F122

8

25E7

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

25E8

RTD #8 TRIP TEMPERATURE

1 to 250

1

°C

F1

90

25E9

RTD #8 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #9

2620

RTD #9 APPLICATION

0 to 4

1

F121

2

2621

RTD #9 ALARM

0 to 2

1

F115

0

2622

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2623

RTD #9 ALARM TEMPERATURE

1 to 250

1

°C

F1

80

2624

RTD #9 ALARM EVENTS

0 to 1

1

F105

0

2625

RTD #9 TRIP

0 to 2

1

F115

0

2626

RTD #9 TRIP VOTING

1 to 12

1

F122

9

2627

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2628

RTD #9 TRIP TEMPERATURE

1 to 250

1

°C

F1

90

2629

RTD #9 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #10

2660

RTD #10 APPLICATION

0 to 4

1

F121

2

2661

RTD #10 ALARM

0 to 2

1

F115

0

2662

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2663

RTD #10 ALARM TEMPERATURE

1 to 250

1

°C

F1

80

2664

RTD #10 ALARM EVENTS

0 to 1

1

F105

0

2665

RTD #10 TRIP

0 to 2

1

F115

0

2666

RTD #10 TRIP VOTING

1 to 12

1

F122

10

2667

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2668

RTD #10 TRIP TEMPERATURE

1 to 250

1

°C

F1

90

2669

RTD #10 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #11

26A0

RTD #11 APPLICATION

0 to 4

1

F121

4

26A1

RTD #11 ALARM

0 to 2

1

F115

0

26A2

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

26A3

RTD #11 ALARM TEMPERATURE

1 to 250

1

°C

F1

80

26A4

RTD #11 ALARM EVENTS

0 to 1

1

F105

0

Table 6–1: 489 MEMORY MAP (SHEET 17 OF 24)