4.10 S9 THERMAL MODEL

4 SETPOINTS

4

4.10.2 MODEL SETUP

a) DESCRIPTION

PATH: SETPOINTS

ÖØ

S9 THERMAL MODEL

Ö

MODEL SETUP

„ MODEL SETUP
„ [ENTER] for more

ENABLE THERMAL

MODEL: No

Range: No, Yes

OVERLOAD PICKUP

LEVEL: 1.01 x FLA

Range: 1.01 to 1.25

× FLA in steps of 0.01

UNBALANCE BIAS

K FACTOR

Range: 0 to 12 in steps of 1

A value of "0" effectively defeats this feature

COOL TIME CONSTANT

ONLINE: 15 min.

Range: 0 to 500 min. in steps of 1

COOL TIME CONSTANT

OFFLINE: 30 min.

Range: 0 to 500 min. in steps of 1

HOT/COLD SAFE

STALL RATIO: 1.00

Range: 0.01 to 1.00 in steps of 0.01

ENABLE RTD

BIASING: No

Range: No, Yes

RTD BIAS

MINIMUM: 40°C

Range: 0 to 250°C in steps of 1

Seen only if

ENABLE RTD BIASING

is "Yes"

RTD BIAS CENTER

POINT: 130°C

Range: 0 to 250°C in steps of 1

Seen only if

ENABLE RTD BIASING

is "Yes"

RTD BIAS

MAXIMUM: 155°C

Range: 0 to 250°C in steps of 1

Seen only if

ENABLE RTD BIASING

is "Yes"

SELECT CURVE STYLE:

Standard

Range: Standard, Custom, Voltage Dependent

STANDARD OVERLOAD

CURVE NUMBER: 4

Range: 1 to 15 in steps of 1. Seen only if

SELECT

CURVE STYLE

is "Standard"

TIME TO TRIP AT

1.01 x FLA: 17414.5 s

Range: 0.5 to 99999.9 in steps of 0.1. Seen only if

SELECT CURVE STYLE

is "Standard"

TIME TO TRIP AT

20.0 x FLA: 20.0 x FLA

Range: 0.5 to 99999.9 in steps of 0.1. Seen only if

SELECT CURVE STYLE

is "Standard"

MINIMUM ALLOWABLE

VOLTAGE: 80%

Range: 70 to 95% in steps of 1. Seen only if

SELECT

CURVE STYLE

is "Voltage Dependent"

STALL CURRENT @ MIN

VOLTAGE: 4.80 x FLA

Range: 2.00 to 15.00

× FLA in steps of 0.01.Seen only if

SELECT CURVE STYLE

is Voltage Dependent

SAFE STALL TIME @

MIN VOLTAGE: 20.0 s

Range: 0.5 to 999.9 in steps of 0.1. Seen only if

SELECT

CURVE STYLE

is "Voltage Dependent"

ACCEL. INTERSECT

@

MIN VOLT: 3.80 x FLA

Range: 2.00 to STALL CURRENT @ MIN VOLTAGE in

steps of 0.01. Seen only if

SELECT CURVE

STYLE

is "Voltage Dependent"

STALL CURRENT @ 100%

VOLTAGE: 6.00 x FLA

Range: 2.00 to 15.00

× FLA in steps of 0.01. Seen only if

SELECT CURVE STYLE

is Voltage Dependent

SAFE STALL TIME @

100% VOLTAGE: 10.0 s

Range: 0.5 to 999.9 in steps of 0.1. Seen only if

SELECT

CURVE STYLE

is "Voltage Dependent"

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising