6-28

489 Generator Management Relay

GE Multilin

6.3 MODBUS MEMORY MAP

6 COMMUNICATIONS

6

2846

TIME TO TRIP AT 20.0

× FLA

5 to 999999

1

s

F10

5

2848

MINIMUM ALLOWABLE VOLTAGE

70 to 95

1

%

F1

80

2849

STALL CURRENT @ MIN VOLTAGE

200 to 1500

1

× FLA

F3

480

284A

SAFE STALL TIME @ MIN VOLTAGE

5 to 9999

1

s

F2

200

284B

ACCEL. INTERSECT @ MIN VOLT

200 to 1500

1

× FLA

F3

380

284C

STALL CURRENT @ 100% VOLTAGE

200 to 1500

1

× FLA

F3

600

284D

SAFE STALL TIME @ 100% VOLTAGE

5 to 9999

1

s

F2

100

284E

ACCEL. INTERSECT @ 100% VOLT

200 to 1500

1

× FLA

F3

500

THERMAL MODEL / THERMAL ELEMENTS

2900

THERMAL MODEL ALARM

0 to 2

1

F115

0

2901

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2902

THERMAL ALARM LEVEL

10 to 100

1

%Used

F1

75

2903

THERMAL MODEL ALARM EVENTS

0 to 1

1

F105

0

2904

THERMAL MODEL TRIP

0 to 2

1

F115

0

2905

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

MONITORING / TRIP COUNTER

2A00

TRIP COUNTER ALARM

0 to 2

1

F115

0

2A01

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2A02

TRIP COUNTER ALARM LEVEL

1 to 50000

1

Trips

F1

25

2A03

TRIP COUNTER ALARM EVENTS

0 to 1

1

F105

0

MONITORING / BREAKER FAILURE

2A20

BREAKER FAILURE ALARM

0 to 2

1

F115

0

2A21

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2A22

BREAKER FAILURE LEVEL

5 to 2000

1

× CT

F3

100

2A23

BREAKER FAILURE DELAY

10 to 1000

10

ms

F1

100

2A24

BREAKER FAILURE ALARM EVENTS

0 to 1

1

F105

0

MONITORING / TRIP COIL MONITOR

2A30

TRIP COIL MONITOR ALARM

0 to 2

1

F115

0

2A31

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2A32

TRIP COIL MONITOR ALARM EVENTS

0 to 1

1

F105

0

MONITORING / VT FUSE FAILURE

2A50

VT FUSE FAILURE ALARM

0 to 2

1

F115

0

2A51

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2A52

VT FUSE FAILURE ALARM EVENTS

0 to 1

1

F105

0

MONITORING / CURRENT DEMAND

2A60

CURRENT DEMAND PERIOD

5 to 90

1

min

F1

15

2A61

CURRENT DEMAND ALARM

0 to 2

1

A

F115

0

2A62

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

A

F50

16

2A63

CURRENT DEMAND LIMIT

10 to 2000

1

× FLA

F14

125

2A65

CURRENT DEMAND ALARM EVENTS

0 to 1

1

A

F105

0

MONITORING / MW DEMAND

2A70

MW DEMAND PERIOD

5 to 90

1

min

F1

15

2A71

MW DEMAND ALARM

0 to 2

1

F115

0

2A72

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2A73

MW DEMAND LIMIT

10 to 200

1

× Rated

F14

125

2A75

MW DEMAND ALARM EVENTS

0 to 1

1

F105

0

MONITORING / Mvar DEMAND

2A80

Mar DEMAND PERIOD

5 to 90

1

min

F1

15

2A81

Mar DEMAND ALARM

0 to 2

1

F115

0

2A82

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2A83

Mar DEMAND LIMIT

10 to 200

1

× Rated

F14

125

2A85

Mar DEMAND ALARM EVENTS

0 to 1

1

F105

0

MONITORING / MVA DEMAND

2A90

MVA DEMAND PERIOD

5 to 90

1

min

F1

15

2A91

MVA DEMAND ALARM

0 to 2

1

F115

0

2A92

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2A93

MVA DEMAND LIMIT

10 to 200

1

× Rated

F14

125

2A95

MVA DEMAND ALARM EVENTS

0 to 1

1

F105

0

MONITORING / PULSE OUTPUT

2AB0

POS. kWh PULSE OUT RELAYS (2-5)

1 to 4

1

F50

0

2AB1

POS. kWh PULSE OUT INTERVAL

1 to 50000

1

F1

10

2AB2

POS. kvarh PULSE OUT RELAYS (2-5)

1 to 4

1

F50

0

2AB3

POS. kvarh PULSE OUT INTERVAL

1 to 50000

1

F1

10

2AB4

NEG. kvarh PULSE OUT RELAYS (2-5)

1 to 4

1

F50

0

2AB5

NEG. kvarh PULSE OUT INTERVAL

1 to 50000

1

F1

10

2AB6

PULSE WIDTH

200 to 1000

1

F1

200

Table 6–1: 489 MEMORY MAP (SHEET 19 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33