GE 489 User Manual

Page 211

Advertising
background image

GE Multilin

489 Generator Management Relay

6-49

6 COMMUNICATIONS

6.5 DNP POINT LISTS

6

83

F1

Reactive Power (Mar)

Class 2

Note 8

84

F1

Reactive Power (kvar)

Class 2

Note 8

85

F1

Apparent Power (MVA)

Class 2

Note 8

86

F1

Apparent Power (kVA)

Class 2

Note 8

87

F1

Hottest Stator RTD

Class 2

Note 3

88

F4

Hottest Stator RTD Temperature (°C)

Class 2

89

F4

RTD #1 Temperature (°C)

Class 2

90

F4

RTD #2 Temperature (°C)

Class 2

91

F4

RTD #3 Temperature (°C)

Class 2

92

F4

RTD #4 Temperature (°C)

Class 2

93

F4

RTD #5 Temperature (°C)

Class 2

94

F4

RTD #6 Temperature (°C)

Class 2

95

F4

RTD #7 Temperature (°C)

Class 2

96

F4

RTD #8 Temperature (°C)

Class 2

97

F4

RTD #9 Temperature (°C)

Class 2

98

F4

RTD #10 Temperature (°C)

Class 2

99

F4

RTD #11 Temperature (°C)

Class 2

100

F4

RTD #12 Temperature (°C)

Class 2

101

F1

Current Demand

Class 2

Note 7

102

F1

MW Demand

Class 2

Note 8

103

F1

kW Demand

Class 2

Note 8

104

F1

Mvar Demand

Class 2

Note 8

105

F1

kvar Demand

Class 2

Note 8

106

F1

MVA Demand

Class 2

Note 8

107

F1

kVA Demand

Class 2

Note 8

108

F1

Peak Current Demand

Class 2

Note 7

109

F1

Peak MW Demand

Class 2

Note 8

110

F1

Peak kW Demand

Class 2

Note 8

111

F1

Peak Mvar Demand

Class 2

Note 8

112

F1

Peak kvar Demand

Class 2

Note 8

113

F1

Peak MVA Demand

Class 2

Note 8

114

F1

Peak kVA Demand

Class 2

Note 8

115

F12

Analog Input 1

Class 2

Note 9

116

F12

Analog Input 2

Class 2

Note 9

117

F12

Analog Input 3

Class 2

Note 9

118

F12

Analog Input 4

Class 2

Note 9

119

F1

Tachometer RPM

Class 2

120

F1

Average Generator Load

Class 2

121

F1

Average Negative Sequence Current

Class 2

122

F1

Average Phase-Phase Voltage

Class 2

123

-

User Map Value 1

Note 5

124

-

User Map Value 2

Note 5

↓...

246

-

User Map Value 124

Note 5

247

-

User Map Value 125

Note 5

248

F118

Active Setpoint Group

Class 1

Note 3

249

F13

Positive kWh

Class 2

Table 6–8: ANALOG INPUTS POINT LIST (SHEET 3 OF 4)

INDEX

FORMAT

DESCRIPTION

EVENT CLASS

ASSIGNED TO

NOTES