Table 6–2: data formats (sheet 4 of 5) – GE 489 User Manual

Page 199

Advertising
background image

GE Multilin

489 Generator Management Relay

6-37

6 COMMUNICATIONS

6.3 MODBUS MEMORY MAP

6

F139

Unsigned

16 bit integer

Force operation of relays

F140

16 bits

General Status

F141

16 bits

Output Relay Status

F142

Unsigned

16 bit integer

Thermal Model curve style selection

0 = Standard, 1 = Custom, 2 = Voltage Dependent

F200

Unsigned

16 bit integer

Comm. monitor buffer status

F201

Unsigned

16 bit integer

Curve Reset Type

0 = Instantaneous, 1 = Linear

F202

Unsigned

16 bit integer

Inadvertent energization arming type

0 = U/V and Offline, 1 = U/V or Offline

F206

Unsigned

16 bit integer

Sequential trip type

0 = Low Forward Power, 1 = Reverse Power

F207

Unsigned

16 bit integer

Switch status

0 = Open, 1 = Shorted

F208

Unsigned

16 bit integer

Undervoltage trip element type

0 = Curve, 1 = Definite Time

F209

Unsigned

16 bit integer

Breaker operation type

0 = Breaker Auxiliary a, 1 = Breaker Auxiliary b

F210

Unsigned

16 bit integer

Assignable input selection

Table 6–2: DATA FORMATS (SHEET 4 OF 5)

FORMAT

CODE

TYPE

DEFINITION

VALUE

PARAMETER

VALUE PARAMETER

0

Disabled

5

R5 Alarm

1

R1 Trip

6

R6 Service

2

R2 Auxiliary

7

All Relays

3

R3 Auxiliary

8

No Relays

4

R4 Auxiliary

BIT NO.

PARAMETER

BIT NO.

PARAMETER

Bit 0

Relay in Service

Bit 8

Breaker Open LED

Bit 1

Active Trip Condition

Bit 9

Breaker Closed LED

Bit 2

Active Alarm Condition

Bit 10

Hot Stator LED

Bit 3

Reserved

Bit 11

Neg. Sequence LED

Bit 4

Reserved

Bit 12

Ground LED

Bit 5

Reserved

Bit 13

Loss of Field LED

Bit 6

Reserved

Bit 14

VT Failure LED

Bit 7

Simulation Mode Enabled

Bit 15

Breaker Failure LED

BIT NO.

PARAMETER

BIT NO.

PARAMETER

Bit 0

R1 Trip

Bit 8

Reserved

Bit 1

R2 Auxiliary

Bit 9

Reserved

Bit 2

R3 Auxiliary

Bit 10

Reserved

Bit 3

R4 Auxiliary

Bit 11

Reserved

Bit 4

R5 Alarm

Bit 12

Reserved

Bit 5

R6 Service

Bit 13

Reserved

Bit 6

Reserved

Bit 14

Reserved

Bit 7

Reserved

Bit 15

Reserved

VALUE

PARAMETER

VALUE

PARAMETER

0

Buffer Cleared

4

Illegal Count

1

Received OK

5

Illegal Reg. Addr.

2

Wrong Slave Addr.

6

CRC Error

3

Illegal Function

7

Illegal Data

VALUE

PARAMETER

VALUE

PARAMETER

0

None

4

Input 4

1

Input 1

5

Input 5

2

Input 2

6

Input 6

3

Input 3

7

Input 7

Advertising