GE Multilin

489 Generator Management Relay

1-7

1 INTRODUCTION

1.2 SPECIFICATIONS

1

Elements:

Trip and Alarm

OVERFREQUENCY

Required Voltage:

0.50 to 0.99

× rated voltage in Phase A

Block From Online:

0 to 5 sec. in steps of 1

Pick- up Level:

25.01 to 70.00 in steps of 0.01

Curve Shapes:

1 level alarm, 2 level trip definite time

Time Delay:

0.1 to 5000.0 s in steps of 0.1

Pickup Accuracy:

±0.02 Hz

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip and Alarm

NEUTRAL OVERVOLTAGE (FUNDAMENTAL)

Pick-up Level:

2.0 to 100.0 V secondary in steps of 0.01

Time Delay:

0.1 to 120.0 s in steps of 0.1

Pickup Accuracy:

as per Neutral Voltage Input

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip and Alarm

NEUTRAL UNDERVOLTAGE (3RD HARMONIC)

Blocking Signals:

Low power and low voltage if open delta

Pick-up Level:

0.5 to 20.0 V secondary in steps of 0.01
if open delta VT; adaptive if wye VT

Time Delay:

5 to 120 s in steps of 1

Pickup Accuracy:

as per Neutral Voltage Input

Timing Accuracy:

±3.0 s

Elements:

Trip and Alarm

LOSS OF EXCITATION (IMPEDANCE)

Pickup Level:

2.5 to 300.0

Ω secondary in steps of 0.1

with adjustable impedance offset 1.0 to
300.0

Ω secondary in steps of 0.1

Time Delay:

0.1 to 10.0 s in steps of 0.1

Pickup Accuracy:

as per Voltage and Phase Current Inputs

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip (2 zones using impedance circles)

DISTANCE (IMPEDANCE)

Pickup Levels:

0.1 to 500.0

Ω secondary in steps of 0.1

50 to 85° reach in steps of 1

Time Delay:

0.0 to 150.0 s in steps of 0.1

Pickup Accuracy:

as per Voltage and Phase Current Inputs

Timing Accuracy:

150 ms ±50 ms or ±0.5% of total time

Elements:

Trip (two trip zones)

REACTIVE POWER

Block From Online:

0 to 5000 s in steps of 1

Pick- up Level:

0.02 to 1.50

× rated Mvar

(positive and negative)

Time Delay:

0.2 to 120.0 s in steps of 0.1

Pickup Accuracy:

see power metering

Timing Accuracy:

±100ms or ±0.5% of total time

Elements:

Trip and Alarm

REVERSE POWER

Block From Online:

0 to 5000 s in steps of 1

Pick- up Level:

0.02 to 0.99

× rated MW

Time Delay:

0.2 to 120.0 s in steps of 0.1

Pickup Accuracy:

see power metering

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip and Alarm

LOW FORWARD POWER

Block From Online:

0 to 15000 s in steps of 1

Pick- up Level:

0.02 to 0.99

× rated MW

Time Delay:

0.2 to 120.0 s in steps of 0.1

Pickup Accuracy:

see power metering

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip and Alarm

PULSE OUTPUT

Parameters:

+ kwh, +kvarh, -kvarh

Interval:

1 to 50000 in steps of 1

Pulse Width:

200 to 1000 ms in steps of 1 ms

RTDS 1 TO 12

Pickup:

1 to 250°C in steps of 1

Pickup Hysteresis:

2°C

Time Delay:

3 sec.

Elements:

Trip and Alarm

OVERLOAD / STALL PROTECTION / THERMAL MODEL

Overload Curves:

15 Standard Overload Curves
Custom Curve
Voltage Dependent Custom Curve
(all curves time out against average
phase current)

Curve Biasing:

Phase Unbalance
Hot/Cold Curve Ratio
Stator RTD
Online Cooling Rate
Offline Cooling Rate
Line Voltage

Overload Pickup:

1.01 to 1.25

Pickup Accuracy:

as per Phase Current Inputs

Timing Accuracy:

±100 ms or ±2% of total time

Elements:

Trip and Alarm

OTHER FEATURES

Serial Start/Stop Initiation
Remote Reset (Configurable Digital Input)
Test Input (Configurable Digital Input)
Thermal Reset (Configurable Digital Input)
Dual Setpoints
Pre-Trip Data
Event Recorder
Waveform Memory
Fault Simulation
VT Failure
Trip Counter
Breaker Failure
Trip Coil Monitor
Generator Running Hours Alarm
IRIG-B Failure Alarm

ENVIRONMENTAL

Ambient Operating Temperature: –40°C to +60°C
Ambient Storage Temperature: 40°C to +80°C.
Humidity:

Up to 90%, noncondensing.

Altitude:

Up to 2000 m

Pollution Degree:

2