background image

GE Multilin

489 Generator Management Relay

4-17

4 SETPOINTS

4.4 S3 DIGITAL INPUTS

4

The following chart illustrates the Group 2 (alternate group) setpoints

The active group can be selected using the

ACTIVATE SETPOINT GROUP

setpoint or the assigned digital input (shorting that

input will activate the alternate set of protection setpoints, Group 2). In the event of a conflict between the

ACTIVATE SET-

POINT GROUP

setpoint or the assigned digital input, Group 2 will be activated. The LED indicator on the faceplate of the 489

will indicate when the alternate setpoints are active in the protection scheme. Changing the active setpoint group will be
logged as an event. Independently, the setpoints in either group can be viewed and/or edited using the

EDIT SETPOINT

GROUP

setpoint. Headers for each setpoint message subgroup that has dual settings will be denoted by a superscript num-

ber indicating which setpoint group is being viewed or edited. Also, when a setpoint that has dual settings is stored, the
flash message that appears will indicate which setpoint group setting has been changed.

4.4.8 SEQUENTIAL TRIP

PATH: SETPOINTS

ÖØ

S3 DIGITAL INPUTS

ÖØ

SEQUENTIAL TRIP

During routine shutdown and for some less critical trips, it may be desirable to use the sequential trip function to prevent
overspeed. If an input is assigned to the sequential trip function, shorting that input will enable either a low forward power or
reverse power function. Once the measured 3-phase total power falls below the low forward power level, or exceeds the
reverse power level for the period of time specified, a trip will occur. This time delay will typically be shorter than that used
for the standard reverse power or low forward power elements. The level is programmed in per unit of generator rated MW
calculated from the rated MVA and rated power factor. If the VT type is selected as None, the sequential trip element will
operate as a simple timer. Once the input has been shorted for the period of time specified by the delay, a trip will occur.

The minimum magnitude of power measurement is determined by the phase CT minimum of 2% rated CT primary.
If the level for reverse power is set below that level, a trip or alarm will only occur once the phase current exceeds
the 2% cutoff.

Users are cautioned that a reverse power element may not provide reliable indication when set to a very low setting, partic-
ularly under conditions of large reactive loading on the generator. Under such conditions, low forward power is a more reli-
able element.

2 S5 SETPOINTS

CURRENT ELEMENTS

2 S6 SETPOINTS

VOLTAGE ELEMENTS

2 S7 SETPOINTS

POWER ELEMENTS

2 S8 SETPOINTS

RTD TEMPERATURE

2 S9 SETPOINTS

THERMAL MODEL

2 OVERCURRENT ALARM

2 UNDERVOLTAGE

2 REACTIVE POWER

2 RTD TYPES

2 MODEL SETUP

2 OFFLINE O/C

2 OVERVOLTAGE

2 REVERSE POWER

2 RTD #1

2 THERMAL ELEMENTS

2 INADVERTENT ENERG.

2 VOLTS/HERTZ

2 LOW FORWARD POWER

2 PHASE OVERCURRENT

2 PHASE REVERSAL

2 RTD #12

2 NEGATIVE SEQUENCE

2 UNDERFREQUENCY

2 OPEN RTD SENSOR

2 GROUND O/C

2 NEUTRAL O/V (Fund)

2 RTD SHORT/LOW TEMP

2 PHASE DIFFERENTIAL

2 NEUTRAL O/V (3rd)

2 GROUND DIRECTIONAL

2 LOSS OF EXCITATION

2 HIGH-SET PHASE O/C

2 DISTANCE ELEMENT

„ SEQUENTIAL TRIP
„ [ENTER] for more

ASSIGN DIGITAL

INPUT: None

Range: None, Input 1 to Input 7. If an input is assigned to

the Tachometer, it may not be used here.

SEQUENTIAL TRIP TYPE

Low Forward Power

Range: Low Forward Power, Reverse Power

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

SEQUENTIAL TRIP

LEVEL: 0.05 x Rated MW

Range: 0.02 to 0.99

× Rated MW in steps of 0.01

SEQUENTIAL TRIP

DELAY: 1.0 s

Range: 0.2 to 120.0 s in steps of 0.1