4 neutral voltage (fundamental) accuracy, Neutral voltage (fundamental) accuracy -4 – GE 489 User Manual

Page 216

Advertising
background image

7-4

489 Generator Management Relay

GE Multilin

7.2 HARDWARE FUNCTIONAL TESTS

7 TESTING

7

7.2.3 GROUND (1 A), NEUTRAL, AND DIFFERENTIAL CURRENT ACCURACY

The specification for neutral, differential and 1 A ground current input accuracy is

±0.5% of 2 × CT. Perform the steps below

to verify accuracy.

1.

Alter the following setpoints:

S2 SYSTEM SETUP

Ö

CURRENT SENSING

ÖØ

GROUND CT:

"1A Secondary"

S2 SYSTEM SETUP

Ö

CURRENT SENSING

ÖØ

GROUND CT RATIO:

"1000:1"

S2 SYSTEM SETUP

ÖØ

CURRENT SENSING

Ö

PHASE CT PRIMARY:

"1000 A"

S5 CURRENT ELEMENTS

ÖØ

PHASE DIFFERENTIAL

Ö

PHASE DIFFERENTIAL TRIP:

"Unlatched"

S5 CURRENT ELEMENTS

ÖØ

PHASE DIFFERENTIAL

ÖØ

DIFFERENTIAL TRIP MIN. PICKUP:

"0.1 x CT"

2.

Note: the last two setpoints are needed to view the neutral and the differential current. The trip element will operate
when differential current exceeds 100 A.

3.

Measured values should be

±10 A. Inject (I

A

only) the values shown in the table below into one phase only and verify

accuracy of the measured values. View the measured values in:

A2 METERING DATA

Ö

CURRENT METERING

or press the

key to view the current values when differential trip element is active.

7.2.4 NEUTRAL VOLTAGE (FUNDAMENTAL) ACCURACY

The specification for neutral voltage (fundamental) accuracy is

±0.5% of full scale (100 V). Perform the steps below to verify

accuracy.

1.

Alter the following setpoints:

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

ÖØ

NEUTRAL VOLTAGE TRANSFORMER:

"Yes"

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

ÖØ

NEUTRAL V.T. RATIO:

"10.00:1"

S2 SYSTEM SETUP

ÖØ

GEN. PARAMETERS

ÖØ

GENERATOR NOMINAL FREQUENCY:

"60 Hz"

2.

Measured values should be

±5.0 V. Apply the voltage values shown in the table and verify accuracy of the measured

values. View the measured values in:

A2 METERING DATA

ÖØ

VOLTAGE METERING

Table 7–1: NEUTRAL AND GROUND CURRENT TEST RESULTS

INJECTED

CURRENT

1 A UNIT

EXPECTED

CURRENT

READING

MEASURED

GROUND

CURRENT

MEASURED NEUTRAL CURRENT

PHASE A

PHASE B

PHASE C

0.1 A

100 A

0.2 A

200 A

0.5 A

500 A

1 A

1000 A

Table 7–2: DIFFERENTIAL CURRENT TEST RESULTS

INJECTED

CURRENT

EXPECTED CURRENT READING

MEASURED DIFFERENTIAL CURRENT

DIFF. PHASE A

DIFF PHASE B,C

PHASE A

PHASE B

PHASE C

0.1 A

200 A

100 A

0.2 A

400 A

200 A

0.5 A

1000 A

500 A

1 A

2000 A

1000 A

APPLIED NEUTRAL

VOLTAGE AT 60 HZ

EXPECTED NEUTRAL

VOLTAGE

MEASURED NEUTRAL

VOLTAGE

10 V

100 V

30 V

300 V

50 V

500 V

NEXT