6 ge multilin hgf ground accuracy, 7 neutral voltage (3rd harmonic) accuracy, Ge multilin hgf ground accuracy -13 – GE 489 User Manual
Page 225: Neutral voltage (3rd harmonic) accuracy -13

GE Multilin
489 Generator Management Relay
7-13
7 TESTING
7.3 ADDITIONAL FUNCTIONAL TESTS
7
7.3.6 GE MULTILIN HGF GROUND ACCURACY
The specification for GE Multilin HGF 50:0.025 ground current input accuracy is
±0.5% of 2 × CT rated primary (25 A). Per-
form the steps below to verify accuracy.
1.
Alter the following setpoint:
S2 SYSTEM SETUP
Ö
CURRENT SENSING
ÖØ
GROUND CT:
"50:0.025 CT"
2.
Measured values should be
±0.25 A. Inject the values shown in the table below either as primary values into a GE Mul-
tilin 50:0.025 Core Balance CT or as secondary values that simulate the core balance CT. Verify accuracy of the mea-
sured values in:
A2 METERING DATA
Ö
CURRENT METERING
7.3.7 NEUTRAL VOLTAGE (3RD HARMONIC) ACCURACY
The 489 specification for neutral voltage (3rd harmonic) accuracy is
±0.5% of full scale (100 V). Perform the steps below to
verify accuracy.
1.
Alter the following setpoints:
S2 SYSTEM SETUP
ÖØ
VOLTAGE SENSING
ÖØ
NEUTRAL VOLTAGE TRANSFORMER:
"Yes"
S2 SYSTEM SETUP
ÖØ
VOLTAGE SENSING
ÖØ
NEUTRAL V.T. RATIO:
"10.00:1"
S2 SYSTEM SETUP
ÖØ
GEN. PARAMETERS
ÖØ
GENERATOR NOMINAL FREQUENCY:
"60 Hz"
2.
Measured values should be
±5.0 V. Apply the voltage values shown in the table and verify accuracy of the measured
values. View the measured values in:
A2 METERING DATA
ÖØ
VOLTAGE METERING
INJECTED CURRENT
CURRENT READING
PRIMARY 50:0.025 CT
SECONDARY
EXPECTED
MEASURED
0.25 A
0.125 mA
0.25 A
1 A
0.5 mA
1.00 A
5 A
2.5 mA
5.00 A
10 A
5 mA
10.00 A
APPLIED NEUTRAL
VOLTAGE AT 180 HZ
EXPECTED NEUTRAL
VOLTAGE
MEASURED NEUTRAL
VOLTAGE
10 V
100 V
30 V
300 V
50 V
500 V