3 power metering, Power metering -15 – GE 489 User Manual

Page 147

Advertising
background image

GE Multilin

489 Generator Management Relay

5-15

5 ACTUAL VALUES

5.3 A2 METERING DATA

5

5.3.3 POWER METERING

PATH: ACTUAL VALUES

ÖØ

A2 METERING DATA

ÖØ

POWER METERING

The values for power metering appear here. Three-phase total power quantities are displayed here. Watthours and var-
hours are also shown here. Watthours and varhours will not update if a digital input programmed as Test Input is shorted.

An induction generator, by convention generates Watts and consumes vars (+Watts and –vars). A synchro-
nous generator can also generate vars (+vars).

If the

VT CONNECTION TYPE

is programmed as "None", the

THIS FEATURE NOT PROGRAMMED

flash message will appear

when an attempt is made to enter this group of messages.

„ POWER METERING
„ [ENTER] for more

POWER FACTOR:

0.00

Range: 0.01 to 0.99 Lead or Lag, 0.00, 1.00

REAL POWER:

0.000 MW

Range: 0.000 to ±2000.000 MW

REACTIVE POWER:

0.000 Mvar

Range: 0.000 to ±2000.000 Mvar

APPARENT POWER:

0.000 MVA

Range: 0.000 to 2000.000 MVA

POSITIVE WATTHOURS:

0.000 MWh

Range: 0.000 to 4000000.000 MWh

POSITIVE VARHOURS:

0.000 Mvarh

Range: 0.000 to 4000000.000 Mvarh

NEGATIVE VARHOURS:

0.000 Mvarh

Range: 0.000 to 4000000.000 Mvarh