Table 6–2: data formats (sheet 2 of 5) – GE 489 User Manual

Page 197

Advertising
background image

GE Multilin

489 Generator Management Relay

6-35

6 COMMUNICATIONS

6.3 MODBUS MEMORY MAP

6

F107

Unsigned

16 bit integer

Nominal frequency selection

0 = -----, 1 = 60 Hz, 2 = 50 Hz, 3 = 25 Hz

F109

Unsigned

16 bit integer

Breaker status switch type

0 = Auxiliary a, 1 = Auxiliary b

F115

Unsigned

16 bit integer

Alarm / trip type selection

0 = Off, 1 = Latched, 2 = Unlatched

F117

Unsigned

16 bit integer

Reset mode

0 = All Resets, 1 = Remote Reset Only

F118

Unsigned

16 bit integer

Setpoint Group

0 = Group 1, 1 = Group 2

F120

Unsigned

16 bit integer

RTD type

0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel, 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper

F121

Unsigned

16 bit integer

RTD application

0 = None, 1 = Stator, 2 = Bearing, 3 = Ambient, 4 = Other

F122

Unsigned

16 bit integer

RTD voting selection

1 = RTD #1, 2 = RTD #2, 3= RTD #3,..., 12 = RTD #12

F123

Unsigned

16 bit integer

Alarm / trip status

0 = Not Enabled, 1 = Inactive, 2 = Timing Out, 3 = Active Trip, 4 = Latched Trip

F124

Unsigned

16 bit integer

Phase rotation selection

0 = ----, 1 = ABC, 2 = ACB

F126

Unsigned

16 bit integer

Disabled / Enabled selection

0 = Disabled, 1 = Enabled

F127

Unsigned

16 bit integer

Analog output parameter selection

F128

Unsigned

16 bit integer

Overcurrent curve style selection

F129

Unsigned

16 bit integer

Analog input selection

0 = Disabled, 1 = 4-20 mA, 2 = 0-20 mA, 3 = 0-1 mA

F130

Unsigned

16 bit integer

Pickup type

0 = Over, 1 = Under

Table 6–2: DATA FORMATS (SHEET 2 OF 5)

FORMAT

CODE

TYPE

DEFINITION

VALUE

PARAMETER

VALUE

PARAMETER

0

None

22

AB Voltage

1

IA Output Current

23

BC Voltage

2

IB Output Current

24

CA Voltage

3

IC Output Current

25

Average Voltage

4

Avg. Output Current

26

Volts / Hertz

5

Neg. Seq. Current

27

Frequency

6

Averaged Gen. Load

28

Neutral Voltage (3rd)

7

Hottest Stator RTD

29

Power Factor

8

Hottest Bearing RTD

30

Reactive Power (Mvar)

9

Ambient RTD

31

Real Power (MW)

10

RTD #1

32

Apparent Power (MVA)

11

RTD #2

33

Analog Input 1

12

RTD #3

34

Analog Input 2

13

RTD #4

35

Analog Input 3

14

RTD #5

36

Analog Input 4

15

RTD #6

37

Tachometer

16

RTD #7

38

Therm. Capacity Used

17

RTD #8

39

Current Demand

18

RTD #9

40

Mar Demand

19

RTD #10

41

MW Demand

20

RTD #11

42

MVD Demand

21

RTD #12

VALUE

PARAMETER

VALUE

PARAMETER

0

ANSI Extremely Inverse

7

IEC Short Inverse

1

ANSI Very Inverse

8

IAC Extremely Inverse

2

ANSI Normally Inverse

9

IAC Very Inverse

3

ANSI Moderately Inverse

10

IAC Inverse

4

IEC Curve A (BS142)

11

IAC Short Inverse

5

IEC Curve B (BS142)

12

Flexcurve™

6

IEC Curve C (BS142)

13

Definite Time