7-9

7 TESTING

7.3 ADDITIONAL FUNCTIONAL TESTS

7

7.3ADDITIONAL FUNCTIONAL TESTS

7.3.1 OVERLOAD CURVE ACCURACY

The specification for overload curve timing accuracy is

±100 ms or ±2% of time to trip. Pickup accuracy is as per the current

inputs (

±0.5% of 2 × CT when the injected current is less than 2 × CT and ±1% of 20 × CT when the injected current is equal

to or greater than 2

× CT). Perform the steps below to verify accuracy.

1.

Alter the following setpoints:

S2 SYSTEM SETUP

ÖØ

GEN. PARAMETERS

ÖØ

GENERATOR RATED MVA:

"1.04"

S2 SYSTEM SETUP

ÖØ

GEN. PARAMETERS

ÖØ

GENERATOR VOLTAGE PHASE-PHASE:

"600"

(Note: This is equivalent to setting FLA = 1000 A – For testing purposes ONLY!)

S2 SYSTEM SETUP

Ö

CURRENT SENSING

Ö

PHASE CT PRIMARY:

"1000"

S9 THERMAL MODEL

Ö

MODEL SETUP

ÖØ

SELECT CURVE STYLE:

"Standard"

S9 THERMAL MODEL

Ö

MODEL SETUP

ÖØ

OVERLOAD PICKUP LEVEL:

"1.10 x FLA"

S9 THERMAL MODEL

Ö

MODEL SETUP

ÖØ

UNBALANCE BIAS K FACTOR:

"0"

S9 THERMAL MODEL

Ö

MODEL SETUP

ÖØ

HOT/COLD SAFE STALL RATIO:

"1.00"

S9 THERMAL MODEL

Ö

MODEL SETUP

ÖØ

ENABLE RTD BIASING:

"No"

S9 THERMAL MODEL

Ö

MODEL SETUP

ÖØ

STANDARD OVERLOAD CURVE NUMBER:

"4"

S9 THERMAL MODEL

Ö

MODEL SETUP

ÖØ

ENABLE THERMAL MODEL:

"Yes"

S9 THERMAL MODEL

Ö

THERMAL ELEMENTS

ÖØ

THERMAL MODEL TRIP:

"Latched" or "Unlatched"

2.

Any trip must be reset prior to each test. Short the emergency restart terminals momentarily immediately prior to each
overload curve test to ensure that the thermal capacity used is zero. Failure to do so will result in shorter trip times.
Inject the current of the proper amplitude to obtain the values as shown and verify the trip times. Motor load may be
viewed in:

A2 METERING DATA

Ö

CURRENT METERING

3.

Thermal capacity used and estimated time to trip may be viewed in:

A1 STATUS

ÖØ

GENERATOR STATUS

(EQ 7.4)

AVERAGE PHASE

CURRENT DISPLAYED

PICKUP LEVEL

EXPECTED TIME TO

TRIP

TOLERANCE RANGE

MEASURED TIME TO

TRIP (SEC.)

1050 A

1.05

× FLA

never

n/a

1200 A

1.20

× FLA

795.44 sec.

779.53 to 811.35 sec.

1750 A

1.75

× FLA

169.66 sec.

166.27 to 173.05 sec.

3000 A

3.00

× FLA

43.73 sec.

42.86 to 44.60 sec.

6000 A

6.00

× FLA

9.99 sec.

9.79 to 10.19 sec.

10000 A

10.00

× FLA

5.55 sec.

5.44 to 5.66 sec.

NOTE

FLA

Generator Rated MVA

3 Generator Phase-to-Phase Voltage