GE Multilin

489 Generator Management Relay

6-15

6 COMMUNICATIONS

6.3 MODBUS MEMORY MAP

6

0706

ANALOG INPUT 2 MAXIMUM

–50000 to 50000

1

Units

F12

0

0708

ANALOG INPUT 3 MINIMUM

–50000 to 50000

1

Units

F12

0

070A

ANALOG INPUT 3 MAXIMUM

–50000 to 50000

1

Units

F12

0

070C

ANALOG INPUT 4 MINIMUM

–50000 to 50000

1

Units

F12

0

070E

ANALOG INPUT 4 MAXIMUM

–50000 to 50000

1

Units

F12

0

MAINTENANCE / TRIP COUNTERS

077F

TRIP COUNTERS LAST CLEARED (DATE)

N/A

N/A

N/A

F18

N/A

0781

TOTAL NUMBER OF TRIPS

0 to 50000

1

F1

0

0782

DIGITAL INPUT TRIPS

0 to 50000

1

F1

0

0783

SEQUENTIAL TRIPS

0 to 50000

1

F1

0

0784

FIELD-BKR DISCREP. TRIPS

0 to 50000

1

F1

0

0785

TACHOMETER TRIPS

0 to 50000

1

F1

0

0786

OFFLINE OVERCURRENT TRIPS

0 to 50000

1

F1

0

0787

PHASE OVERCURRENT TRIPS

0 to 50000

1

F1

0

0788

NEG.SEQ. OVERCURRENT TRIPS

0 to 50000

1

F1

0

0789

GROUND OVERCURRENT TRIPS

0 to 50000

1

F1

0

078A

PHASE DIFFERENTIAL TRIPS

0 to 50000

1

F1

0

078B

UNDERVOLTAGE TRIPS

0 to 50000

1

F1

0

078C

OVERVOLTAGE TRIPS

0 to 50000

1

F1

0

078D

VOLTS/HERTZ TRIPS

0 to 50000

1

F1

0

078E

PHASE REVERSAL TRIPS

0 to 50000

1

F1

0

078F

UNDERFREQUENCY TRIPS

0 to 50000

1

F1

0

0790

OVERFREQUENCY TRIPS

0 to 50000

1

F1

0

0791

NEUTRAL O/V (FUND) TRIPS

0 to 50000

1

F1

0

0792

NEUTRAL U/V (3rd) TRIPS

0 to 50000

1

F1

0

0793

REACTIVE POWER TRIPS

0 to 50000

1

F1

0

0794

REVERSE POWER TRIPS

0 to 50000

1

F1

0

0795

LOW FORWARD POWER TRIPS

0 to 50000

1

F1

0

0796

STATOR RTD TRIPS

0 to 50000

1

F1

0

0797

BEARING RTD TRIPS

0 to 50000

1

F1

0

0798

OTHER RTD TRIPS

0 to 50000

1

F1

0

0799

AMBIENT RTD TRIPS

0 to 50000

1

F1

0

079A

THERMAL MODEL TRIPS

0 to 50000

1

F1

0

079B

INADVERTENT ENERG. TRIPS

0 to 50000

1

F1

0

079C

ANALOG INPUT 1 TRIPS

0 to 50000

1

F1

0

079D

ANALOG INPUT 2 TRIPS

0 to 50000

1

F1

0

079E

ANALOG INPUT 3 TRIPS

0 to 50000

1

F1

0

079F

ANALOG INPUT 4 TRIPS

0 to 50000

1

F1

0

MAINTENANCE / GENERAL COUNTERS

07A0

NUMBER OF BREAKER OPERATIONS

0 to 50000

1

F1

0

07A1

NUMBER OF THERMAL RESETS

0 to 50000

1

F1

0

MAINTENANCE / TRIP COUNTERS

07A2

LOSS OF EXCITATION 1 TRIPS

0 to 50000

1

F1

0

07A3

LOSS OF EXCITATION 2 TRIPS

0 to 50000

1

F1

0

07A4

GROUND DIRECTIONAL TRIPS

0 to 50000

1

F1

0

07A5

HIGH-SET PHASE O/C TRIPS

0 to 50000

1

F1

0

07A6

DISTANCE ZONE 1 TRIPS

0 to 50000

1

F1

0

07A7

DISTANCE ZONE 2 TRIPS

0 to 50000

1

F1

0

MAINTENANCE / TIMERS

07E0

GENERATOR HOURS ONLINE

0 to 1000000

1

h

F12

0

PRODUCT INFO. / 489 MODEL INFO.

0800

ORDER CODE

0 to 65535

1

N/A

F136

N/A

0801

489 SERIAL NUMBER

3000000 to 9999999

1

F12

3000000

PRODUCT INFO. / CALIBRATION INFO.

0810

ORIGINAL CALIBRATION DATE

N/A

N/A

N/A

F18

N/A

0812

LAST CALIBRATION DATE

N/A

N/A

N/A

F18

N/A

489 SETUP / PREFERENCES

1000

DEFAULT MESSAGE CYCLE TIME

5 to 100

5

s

F2

20

1001

DEFAULT MESSAGE TIMEOUT

10 to 900

1

s

F1

300

1003

PARAMETER AVERAGES CALC. PERIOD

1 to 90

1

min

F1

15

1004

TEMPERATURE DISPLAY

0 to 1

1

F100

0

1005

WAVEFORM TRIGGER POSITION

1 to 100

1

%

F1

25

1006

PASSCODE (WRITE ONLY)

0 to 99999999

1

N/A

F12

0

1008

ENCRYPTED PASSCODE (READ ONLY)

N/A

N/A

N/A

F12

N/A

100A

WAVEFORM MEMORY BUFFER

1 to 16

1

F1

8

Table 6–1: 489 MEMORY MAP (SHEET 6 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33