3 reverse power, Reverse power -47 – GE 489 User Manual

Page 97

Advertising
background image

GE Multilin

489 Generator Management Relay

4-47

4 SETPOINTS

4.8 S7 POWER ELEMENTS

4

4.8.3 REVERSE POWER

PATH: SETPOINTS

ÖØ

S7 POWER ELEMENTS

ÖØ

REVERSE POWER

If enabled, once the magnitude of 3-phase total power exceeds the Pickup Level in the reverse direction (negative MW) for
a period of time specified by the Delay, a trip or alarm will occur. The level is programmed in per unit of generator rated MW
calculated from the rated MVA and rated power factor. If the generator is accelerated from the power system rather than the
prime mover, the reverse power element may be blocked from start for a specified period of time. A value of zero for the
block time indicates that the reverse power protection is active as soon as both current and voltage are measured regard-
less of whether the generator is online or offline. If the VT type is selected as "None" or VT fuse loss is detected, the
reverse power protection is disabled.

The minimum magnitude of power measurement is determined by the phase CT minimum of 2% rated CT primary.
If the level for reverse power is set below that level, a trip or alarm will only occur once the phase current exceeds
the 2% cutoff.

Users are cautioned that a reverse power element may not provide reliable indication when set to a very low setting, partic-
ularly under conditions of large reactive loading on the generator. Under such conditions, low forward power is a more reli-
able element.

„ REVERSE POWER
„ [ENTER] for more

BLOCK REVERSE POWER

FROM ONLINE: 1 s

Range: 0 to 5000 s in steps of 1

REVERSE POWER

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

REVERSE POWER ALARM

LEVEL: 0.05 x Rated MW

Range: 0.02 to 0.99

× Rated MW in steps of 0.01

REVERSE POWER ALARM

DELAY: 10.0 s

Range: 0.2 to 120.0 s in steps of 0.1

REVERSE POWER ALARM

EVENTS: Off

Range: On, Off

REVERSE POWER

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

REVERSE POWER TRIP

LEVEL: 0.05 x Rated MW

Range: 0.02 to 0.99

× Rated MW in steps of 0.01

REVERSE POWER TRIP

DELAY: 20.0 s

Range: 0.2 to 120.0 s in steps of 0.1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

NOTE