7 ground overcurrent, Ground overcurrent -29 – GE 489 User Manual

Page 79

Advertising
background image

GE Multilin

489 Generator Management Relay

4-29

4 SETPOINTS

4.6 S5 CURRENT ELEMENTS

4

4.6.7 GROUND OVERCURRENT

PATH: SETPOINTS

ÖØ

S5 CURRENT ELEMENTS

ÖØ

GROUND O/C

The 489 ground overcurrent feature consists of both an alarm and a trip element. The magnitude of measured ground cur-
rent is used to time out against the definite time alarm or inverse time curve trip. The 489 inverse time curve for this element
may be either ANSI, IEC, or GE Type IAC standard curve shapes. This allows for simplified coordination with downstream
devices. If however, none of these curves shapes is adequate, the FlexCurve™ may be used to customize the inverse time
curve characteristics. If the Ground CT is selected as "None", the ground overcurrent protection is disabled.

The pickup level for the ground current elements is programmable as a multiple of the CT. The 50:0.025 CT
is intended for very sensitive detection of ground faults and its nominal CT rating for the 489 is 50:0.025.

For example, if the ground CT is 50:0.025, a pickup of 0.20 would be 0.20

× 5 = 1 A primary. If the ground CT is 50:0.025, a

pickup of 0.05 would be 0.05

× 5 = 0.25 A primary.

„ GROUND O/C
„ [ENTER] for more

GROUND OVERCURRENT

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

GROUND O/C ALARM

PICKUP: 0.20 x CT

Range: 0.05 to 20.00

× CT in steps of 0.01

GROUND O/C ALARM

DELAY: 0 cycles

Range: 0 to 100 cycles in steps of 1

GROUND OVERCURRENT

ALARM EVENTS: Off

Range: On, Off

GROUND OVERCURRENT

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

GROUND O/C TRIP

PICKUP: 0.20 x CT

Range: 0.05 to 20.00

× CT in steps of 0.01

CURVE SHAPE:

ANSI Extremely Inv.

Range: see Table 4–1: 489 Overcurrent Curve Types on

page 4–21.

FLEXCURVE TRIP TIME

AT 1.03 x PU: 65535 ms

Range: 0 to 65535 ms

Seen only if CURVE SHAPE is Flexcurve

FLEXCURVE TRIP TIME

AT 1.05 x PU: 65535 ms

Range: 0 to 65535 ms

Seen only if CURVE SHAPE is Flexcurve

FLEXCURVE TRIP TIME

AT 20.0 x PU: 65535 ms

Range: 0 to 65535 ms

Seen only if CURVE SHAPE is set to Flexcurve

OVERCURRENT CURVE

MULTIPLIER: 1.00

Range: 0.00 to 1000.00 in steps of 0.01

OVERCURRENT CURVE

RESET: Instantaneous

Range: Instantaneous, Linear

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE